INSP-Final Inspection | 7/6/2007 | 7/6/2007 | 7/6/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/3/2007 | 7/6/2007 | 7/6/2007 | A | CANC |
Troy Cobbley
|
|
|
scotty; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang
|
INSP-Final Inspection | 7/2/2007 | 7/3/2007 | 7/3/2007 | P | FAIL |
Troy Cobbley
|
|
|
The east riser flow switch still did not operate and the company that was to perform the manometer test did not show up.
|
INSP-Alarm Testing | 5/23/2007 | 5/29/2007 | 5/29/2007 | A | FAIL |
Troy Cobbley
|
|
|
See the correction notice for items that did not pass. The spacing of the ceiling mount a/v's are still not code compliant.
|
INSP-Final Inspection | 4/25/2007 | 4/26/2007 | 4/26/2007 | A | FAIL |
Troy Cobbley
|
|
|
I inspected the second floor a/v's for operation. I also inspected the additional strobes added in the storage areas. See the original correction notice for items remaining that need inspection.
|
(F) Reprint permit | | | 3/21/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/21/2007 | | DONE |
|
|
|
|
Alarm Plan Check | 3/20/2007 | | 3/20/2007 | | PASS |
|
|
|
Fire Alarm Review 4th
|
Alarm Plan Check | 3/20/2007 | | 3/20/2007 | | PASS |
|
|
|
Fire Alarm Review Plan Modification
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/20/2007 | | |
|
|
|
Ready for Issue. Plan Modification
|
Inspection Record Card- Fire | 3/20/2007 | | 3/20/2007 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/20/2007 | | DONE |
|
|
|
|
Telephone call | | | 3/20/2007 | | DONE |
|
|
|
call to dave whitting, left msg on ans mach., permit ready to p/u and fees $110.25
|
Case Summary | | | 3/20/2007 | | |
|
|
|
|
Case Summary | | | 3/20/2007 | | |
|
|
|
|
Plan resubmittals received | | | 3/19/2007 | | |
|
|
|
|
Plan assigned to (Mike) | 3/19/2007 | | 3/19/2007 | | DONE |
|
|
|
|
Case Summary | | | 3/19/2007 | | DONE |
|
|
|
|
INSP-Final Inspection | 3/5/2007 | 3/5/2007 | 3/5/2007 | P | FAIL |
Troy Cobbley
|
|
|
We finished testing the duct smoke detectors. One detector located in the 2nd floor break room is mounted in a 90. It will need to be relocated or provide a manometer test. The two tamper switches for both risers did not operate. The PIV tamper did.The west side wet system flow switch operated correctly but the east side inspectors test did not have the correct orfice installed and will need to be retested. To finish project the items listed above need corrected and the notification circuits need to be tested as far as voltage drop and trouble signals as well as device spacing and sound levels. Battery calcs have not been done/verified yet either.
|
INSP-Final Inspection | 3/1/2007 | 3/2/2007 | 3/2/2007 | A | FAIL |
Troy Cobbley
|
|
|
The items tested today were three duct smoke detectors. Mike Timmerman accompanied me on this inspection and verified that additional strobes will be required in the stock rooms due to blockage by the racks. Mike and I also pointed out overspacing of strobes in the retail area.
|
INSP-Final Inspection | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | FAIL |
Troy Cobbley
|
|
|
Items tested today include the phone lines, verified correct panel, interconnection of the six NAC panels to the FACP and tested all manual pull stations.
|
INSP-Alarm Testing | 2/26/2007 | 2/28/2007 | 2/28/2007 | A | FAIL |
Troy Cobbley
|
|
|
The only item tested was the first floor a/v's. Many are overspaced. Strobes are lacking in the corridors formed by the full height racks in the stockrooms. THe racks also form corridors without a/v's within 15' of the ends. Also noted some offices on the second floor that have well over one person in them and not a/v's. No sound levels have been verified yet or end of line voltage drops.
|
Issue and Print Permit | | | 12/6/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 8/22/2006 | | 11/24/2006 | | PASS |
|
|
|
11/24/2006 13:32:55 MWT - activity updated through activity FIRA22 from case FIR06-00466.
|
Plan assigned to (Mike) | 10/24/2006 | | 11/24/2006 | | PASS |
|
|
|
11/24/2006 13:32:55 MWT - activity updated through activity FIRA22 from case FIR06-00466.
|
Alarm Plan Check | 11/24/2006 | | 11/24/2006 | | PASS |
|
|
|
4th Fire Alarm Review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/24/2006 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 11/24/2006 | | 11/24/2006 | | DONE |
|
|
|
|
Telephone call | | | 11/24/2006 | | DONE |
|
|
|
lft vm with recept ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/24/2006 | | |
|
|
|
|
Plan resubmittals received | | | 11/13/2006 | | |
|
|
|
|
Telephone call | | | 10/26/2006 | | DONE |
|
|
|
lft vm for dave whitting ###-#### that permit needs resbumittal - return to applicant
|
Alarm Plan Check | 10/24/2006 | | 10/25/2006 | | FAIL |
|
|
|
3rd Fire Alarm Review
|
Plan resubmittals received | | | 10/19/2006 | | |
|
|
|
|
Alarm Plan Check | | | 8/31/2006 | | FAIL |
|
|
|
Plans reviewed and failed by F. Varle. Review comments faxed to ADT, Dave Whiting.
|
Miscellaneous action | | | 8/22/2006 | | DONE |
|
|
|
plans Fed-exed to FV for review
|
Miscellaneous action | | | 8/14/2006 | | DONE |
|
|
|
Dave Whiting came in and re-organized the resubmited plans into complete sets; added notations to identify and clarify plan modifications. New plans are completely revised form original plans.; therefore allowed Dave to take the orignal plans which are no longer applicable. Plans now ready for review.
|
Plan resubmittals received | | | 7/20/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/17/2006 | | FAIL |
|
|
|
Phoned jody Congleton (ADT designer) and gave the following comments. See Below.
Left a message for Dave Whiting (ADT) to check the website for the comments.
1) Plans must be 1/8" scale (therefore a complete review cannot be accomplished, and additional comments may follow the 2nd submittal.)
2) Manual pull station locations, install per NFPA 72.
3) Possible insufficient visual coverage in areas.
4) Possible insufficient audibility in mech/elec areas.
5) Storage areas should include rack and heights. Unacceptable to include note "Place horn strobes for best coverage".
6) Missing battery box cut sheet
No further review has been completed.
|
Application received | | | 6/22/2006 | | |
|
|
|
|
Case Summary | | | 6/22/2006 | | DONE |
|
|
|
|