Permit NumberFIR06-00472
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 412 S 13TH ST
Project NameSPR PLAZA MIXED USE-RESIDENTIA
Customer Number 
ePlanReview 
Description
PLAZA MIXED USED - (SECTION 2 OF 2) - This portion of the building contains 17 units, and is 25,764-ft/2. A two hour fire wall (also used as a horizontal exit) will be constructed to divide this 42 unit, 61,812-ft/2, 5 story, wood framed apartment building into two separate buildings, above a Type I-A parking garage, per City Ordinance 4-16. Refer to BLD05-02204 for the other side of the fire wall. Refer to BLD05-00926 for the parking garage. This building is fully fire sprinklered per Boise City Ordinance.

The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was permitted under FIR06-00262. The lower parking garage piping (include riser and stand-piping supply) is permitted under FIR06-00365. This permit is attached to building permit: BLD06-02750.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/31/20078/1/20078/2/2007APASS
DetailsForrest France
Field inspection activity for this permit logged under project related fire sprinkler permit FIR06-00639, permit is acceptable for final, inspections passed.
Sprinkler Plan Check  7/31/2007 PASS
Plans for this Section 2 area were approved by B. Johnson 10/5/06 under the permit resubmittal for Section 1 (FIR06-00639); work for both Section 1 and Section 2 was shown on the same set of plans and submitted only under FIR06-00639. Consequently, this permit was not approved or issued at that time. The error was discovered and resolved at the time of the final inspection. The fee for this permit was included in the total number of heads charged under the Section 1 permit (1198), so no additional fee applies to this permit. This permit can now be issued with no fee charged.
PLANS/APPL TAKEN TO FRONT DESK  7/31/2007 DONE
Issue and Print Permit  7/31/2007 DONE
Changed to issue status as all plans were inspected and approved under fir06-00639//All fees paid on fir06-00639//7/31/07 BAS
Meeting  7/27/2007 DONE
Per onsite meeting 7/27/07, Deputy Chief Dave Hanneman, Fire Marshal, approved standpipes in stairwells only, as acceptable to serve the horizontal exit separating section 1and Section 2.
Telephone call  7/23/2007 DONE
Received telcon from John Venche, outside designer for Commercial Fire. Explained the lack of resbumitted plans under this permit number which shows a denied plan review dated 7/13/06 addressing a number of deficiencies including missing Standpipe connections at the horizontal Exit fire wall openings on each level, detailed under comment # 5 of Bill Alexander's plan review). John thought this had been addressed but will look into it further. I indicated we need a resubmittal under this permit addressing all the resubmittal items on Bill's review; he will handle it. Also discussed with Forrest France, who confirmed the SP's were not shown on plans or installed.
Telephone call  7/20/2007 DONE
I called John at Commercial Fire and explained that this permit is still in the Review/Failed status. Item 5 on the list of items to be addressed on the resubmittal is the stanpipes at teh horizontal exit wall. An early start was granted about a month later, but no resubmittal was ever made and according to the building inspector, the sprinkler system was installed without any standpipes at the horizontal exit. John will investigate and follow up to ensure the plans get resubmitted and any deficiencies get corrected. He realizes the urgency due to this currently being under a TOC.
Case Summary  7/20/2007  
Case Summary  7/20/2007  
Telephone call  6/27/2007 DONE
Returned phone message from John, of comercial fire , regarding change in fire sprinkler plan design due to the projects occupancy changing from original use. Left message for John.
Telephone call  6/27/2007 DONE
Spoke with John of commercail fire explaining why the sprinkler permit is not finaled. The building has a TOC unitl the basement system is complete.
INSP-Final Inspection5/1/20075/1/20075/1/2007 PART
Approved for TOC; sprinkler installation not completed in bsmt parking area.
Miscellaneous action  8/25/2006 DONE
Approved Early Start request from Commercial Fire for scope of work: limited to rough-in of lines and mains only, from 5th floor down.
Sprinkler Plan Check6/26/2006 7/13/2006 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  7/13/2006 DONE
Took failed submittal packages (4) to permit desk for returning and required corrections.
Telephone call  7/13/2006 DONE
tlk to john vencne that permit failed and needs to be picked up
Telephone call  7/13/2006 DONE
plans failed gave to customer
Case Summary  6/26/2006  
Application received  6/26/2006  
Plan assigned to (Bill)6/26/2006