Case Summary | | | 2/3/2015 | | DONE |
|
|
|
|
Case Summary | | | 1/30/2015 | | DONE |
|
|
|
|
DOC - Permit Expired | 6/11/2010 | 6/11/2010 | 6/11/2010 | P | PASS |
Forrest France
|
|
|
Tenant has relocated, building is vacant. Permit expired- IFC 2006 sec. 105.3.1
|
FIR-Aging Inspection | 6/7/2010 | 6/7/2010 | 6/11/2010 | | DONE |
Forrest France
|
|
|
Site visit completed.
|
FIR-Aging Inspection | 3/27/2008 | 3/27/2008 | 3/28/2008 | P | DONE |
Forrest France
|
|
|
Peak alarm to schedule testing for final acceptance of permit work.
|
INSP-Sprinkler Rough-in | 6/30/2006 | 7/3/2006 | 7/3/2006 | A | PART |
Forrest France
|
|
|
Preliminary alarm inspection to verify functionality of the new FA panel. Alarm work per the scope of the permit is not yet completed at this time. Testing done today included panel batteries, phone lines, tampers at riser, wet flow, outside bell, and signal verification. AC power loss did not report to monitoring company as required, also need to provide a lock at the breaker. Remainder of alarm work to be tested at next inspection.
|
Plan assigned to (Mary) | 6/27/2006 | | 6/29/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/29/2006 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/29/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 6/29/2006 | | 6/29/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/29/2006 | | DONE |
|
|
|
|
Telephone call | | | 6/29/2006 | | DONE |
|
|
|
lft ms with secretary for bill herbert ###-#### that permit and fees are ready to be picked up
|
Issue and Print Permit | | | 6/29/2006 | | DONE |
|
|
|
|
Application received | | | 6/27/2006 | | |
|
|
|
|