INSP-Final Inspection | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 8/17/2006 | | |
|
|
|
|
INSP-Final Inspection | 8/15/2006 | 8/16/2006 | 8/16/2006 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled.
|
Override - Parcel Holds | | | 8/15/2006 | | |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2006 | 8/2/2006 | 8/2/2006 | A | PART |
Forrest France
|
|
|
Hydrostatic test for the new rack sprinklers at three areas is satisfactory, items on previous c/n have been verified for completion, added sprinklers at halo above the mountain are acceptable. Need to perform forward flow, test new tampers at the backflow, noted the ball drip at the FDC is leaking.
|
INSP-Sprinkler Rough-in | 8/1/2006 | 8/1/2006 | 8/2/2006 | P | DEFR |
Forrest France
|
|
|
Inspection to be completed 8/2
|
INSP-Sprinkler Rough-in | 7/27/2006 | 7/28/2006 | 7/28/2006 | P | PART |
Forrest France
|
|
|
OH rough-in inspection for concealed upright heads at entrance to the bargain cave and EC11 head drops in ceiling tile at retail area as marked on plans are okay to cover. Inspection for heads in racks below walkway in the storage area are acceptable except as marked on plan including missing coverage at one area requiring an additional head, heads at two locations are blocked, one head needs to be replaced due to missing liquid in glass bulb, need to install head guards at all locations where uprights are subject to mechanical damage in the racking system.
|
Plan assigned to (Bill) | 7/17/2006 | | 7/24/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 7/17/2006 | | 7/24/2006 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/24/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/24/2006 | | DONE |
|
|
|
tlk to lily ###-#### that permit and fees are ready to be picked up
|
Plan resubmittals received | | | 7/17/2006 | | |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 6/15/2006 | | 7/5/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/15/2006 | | 7/5/2006 | | PART |
Bill Alexander
|
|
|
Re-Submittals Of The Following Items Are Required:
1. Rack area storage between grids #1 thru 2, "C" thru "K" cannot be accepted as designed. This area (calc are #1 and 7) have been designed with the mezzanine deck as a ceiling, and the protection design below the mezzanine level for OH-2 density (misc. storage). The roof also needs verified for 20'-0" storage of class IV commodities, in single row racks with 4'-0" aisles.
2. Include clarification of rack shelves addressed in Design Area #1 throughout.
3. The pallet/rack storage area south of "K", between columns "1 thru "4" needs clarification. Provide the quantity of pallet piles anticipated in this design area verifying for possible IFC building requirements addressed in IFC Chapter 23.
4. Provide forward flow piping and appurtenance for the system riser and include it on the plan.
5. Provide clarification of obstructed construction for Areas 1, 2, 3, 4, 5, 6, 7, 8, 9 and 10.
6. Plan FP-6, System #4 design calc details label needs some corrections.
a. Change 1500-ft/2 to: 2000-ft/2.
b. Change Table 12.9.1.2a to: 12.1.9.1.2(a).
7. Provide a required calculation graph for each system area verifying.
8. Provide head elevation above the floor in the "Sprinkler Head Analysis" reports.
9. Plan FP3, "Camo/Hunting," FP-4 "Casual," has a small room which is not identified and/or protected. Identify and clarify the use of this room.
10. Clarify building column protection, which will be required in all areas of racks where building columns are located within the racks exceeding 12'-0" in height. (NFPA 13-12.3.1.7.1[C])
|
Miscellaneous action | | | 7/5/2006 | | DONE |
|
|
|
Returned plans for corrections with apporved FIR06-00452 (Canopy).
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/5/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/5/2006 | | 7/5/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/5/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/5/2006 | | DONE |
|
|
|
lft ms with lily ###-#### that permit and fees are ready to be picked up
|
Application received | | | 6/15/2006 | | |
|
|
|
|