INSP-Final Inspection | 8/2/2006 | 8/3/2006 | 8/3/2006 | A | PASS |
Forrest France
|
|
|
Fire alarm permit passed, note: record of completion forms not available for signature on site.
|
INSP-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 | P | FAIL |
Forrest France
|
|
|
HVAC duct detector incorrectly reports as alarm condition and is not identified correctly at remote station monitoring.
|
INSP-Final Inspection | 7/27/2006 | 7/27/2006 | 7/27/2006 | P | FAIL |
Troy Cobbley
|
|
|
No test performed since the gas was not turned on yet.
|
Issue and Print Permit | | | 7/27/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/14/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/14/2006 | | 7/14/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/14/2006 | | DONE |
|
|
|
jodi@###-####/told permit was ready, permit#, project address, & fee
|
Alarm Plan Check | 7/13/2006 | | 7/13/2006 | | PASS |
|
|
|
Plans approved subject to satisfactory inspection and field verification of 4-hour battery capacity with addition of new duct smoke detector.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/13/2006 | | DONE |
|
|
|
Ready to issue
|
Application received | | | 7/7/2006 | | |
|
|
|
|
Case Summary | | | 7/7/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 7/7/2006 | | | | |
|
|
|
|