| INSP-Final Inspection | 7/16/2007 | 7/16/2007 | 7/17/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
| INSP-Final Inspection | 5/1/2007 | 5/1/2007 | 5/1/2007 | P | FAIL |
Forrest France
|
|
|
Tamper switch at the first floor control valve still does not function, weatherproof covers at the 5th floor outdoor notification devices are not yet installed, provide map at the panel as discussed.
|
| INSP-Alarm Testing | 5/1/2007 | 5/1/2007 | 5/1/2007 | | PART |
|
|
|
Approved for TOC. Need final Test Certificate.
|
| INSP-Final Inspection | 4/27/2007 | 4/30/2007 | 4/30/2007 | A | PART |
Forrest France
|
|
|
Remainder of fire alarm system testing completed today, need to provide map at the panel, provide weatherproof protection for the outdoor 5th floor notification devices, repair and retest first floor fire sprinkler tamper switch.
|
| INSP-Final Inspection | 4/26/2007 | 4/27/2007 | 4/27/2007 | A | PART |
Forrest France
|
|
|
Tested previously noted correction items at unit 210 and 312. Open horn circut #3 on the panel at time of inspection due to contractor in process of repair for temporal pattern at the 5th floor notification devices, final pending completion of this issue and satisfactory test of the remaining alarm work.
|
| INSP-Final Inspection | 4/25/2007 | 4/26/2007 | 4/26/2007 | A | PART |
Forrest France
|
|
|
Tested 120V smoke alarms for the dwelling units on the 5th, 4th, 3rd and 2nd floors, noted one device to be moved in unit 210, one device repaired while on site 3rd floor, no access to unit 312, verified signals recieved and corrected descriptor for the waterflow alarms.
|
| INSP-Final Inspection | 4/24/2007 | 4/25/2007 | 4/25/2007 | A | PART |
Forrest France
|
|
|
AFS monitoring, FACP, nac panels, first floor notification, detection and initiation tested today. Noted items in need of correction including correct size batteries at the main panel, dB level in the trash chute rooms, the mini horns in the residential units do not produce the required temporal pattern per review notes or NFPA 72, no elevator devices tested at this time, list of signals recieved to be verified at next scheduled inspection.
|
| Alarm Plan Check | 4/23/2007 | | 4/23/2007 | | PASS |
|
|
|
Fire Alarm Plan Modification 2nd Review
|
| PLANS/APPL TAKEN TO FRONT DESK | | | 4/23/2007 | | |
|
|
|
Ready for Issue
|
| Permit Ready to Issue | | | 4/23/2007 | | DONE |
|
|
|
|
| Telephone call | | | 4/23/2007 | | DONE |
|
|
|
call to lynde, permit ready to p/u and no fee, left msg on vm
|
| Inspection Record Card- Fire | 4/23/2007 | | 4/23/2007 | | DONE |
|
|
|
|
| (F) Reprint permit | | | 4/23/2007 | | DONE |
|
|
|
|
| CHANGE STATUS TO (ISS) | | | 4/23/2007 | | DONE |
|
|
|
|
| Plan resubmittals received | | | 4/20/2007 | | |
|
|
|
PLan Mod per Mike Timmerman
|
| Plan assigned to (Mike) | 4/20/2007 | | 4/20/2007 | | DONE |
|
|
|
|
| FIR-Aging Inspection | 2/22/2007 | 2/22/2007 | 2/23/2007 | | DONE |
Forrest France
|
|
|
Project is still under construction.
|
| Plan assigned to (SAM) | 7/7/2006 | | 10/9/2006 | | PASS |
|
|
|
10/9/2006 10:30:14 MWT - activity updated through activity FIRA22 from case FIR06-00639.
|
| Issue and Print Permit | | | 8/7/2006 | | DONE |
|
|
|
|
| Alarm Plan Check | | | 7/31/2006 | | PASS |
|
|
|
Approved by FV on 7/16/06; held up by MF due to plan deficiencies; approved to issue based on discussion with FV 7/28/06.
|
| PLANS/APPL TAKEN TO FRONT DESK | | | 7/31/2006 | | DONE |
|
|
|
|
| Permit Ready to Issue | | | 7/31/2006 | | DONE |
|
|
|
|
| Inspection Record Card- Fire | 7/31/2006 | | 7/31/2006 | | DONE |
|
|
|
|
| Telephone call | | | 7/31/2006 | | DONE |
|
|
|
spoke to darcy@###-####/told permit was ready, permit#, project name & address and fee
|
| Miscellaneous action | | | 7/11/2006 | | |
|
|
|
Sent to Floyd Varley.
|
| Application received | | | 7/7/2006 | | |
|
|
|
|
| Case Summary | | | 7/7/2006 | | DONE |
|
|
|
|
| Case Summary | | | 7/7/2006 | | DONE |
|
|
|
|