INSP-Final Inspection | 2/23/2007 | 2/23/2007 | 2/23/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/21/2007 | 2/22/2007 | 2/22/2007 | A | FAIL |
Troy Cobbley
|
|
|
Lower the manual pull station and change the reporting text for the tamper switches
|
INSP-Final Inspection | 2/20/2007 | 2/21/2007 | 2/21/2007 | P | CANC |
Troy Cobbley
|
|
|
Inspection to be rescheduled due to time constraints.
|
(F) Reprint permit | | | 2/8/2007 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 2/8/2007 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 7/7/2006 | | 1/31/2007 | | PASS |
|
|
|
1/31/2007 09:59:58 MWT - activity updated through activity FIRA22 from case FIR06-00499.
|
Plan assigned to (Mike) | 9/8/2006 | | 1/31/2007 | | PASS |
|
|
|
1/31/2007 09:59:58 MWT - activity updated through activity FIRA22 from case FIR06-00499.
|
Plan assigned to (Mike) | 1/25/2007 | | 1/31/2007 | | PASS |
|
|
|
1/31/2007 09:59:58 MWT - activity updated through activity FIRA22 from case FIR06-00499.
|
Alarm Plan Check | 1/31/2007 | | 1/31/2007 | | PASS |
|
|
|
Fire Alarm Plan Modification Review 3rd Review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/31/2007 | | |
|
|
|
Plan Modification Ready for Issue
|
Inspection Record Card- Fire | 1/31/2007 | | 1/31/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/31/2007 | | DONE |
|
|
|
left msg for keith olstrom on ans machine, permit ready to p/u fees $131.25
|
Permit Ready to Issue | | | 1/31/2007 | | DONE |
|
|
|
|
FIR-Aging Inspection | 12/12/2006 | 12/12/2006 | 12/12/2006 | | NR |
Troy Cobbley
|
|
|
Work in progress
|
Issue and Print Permit | | | 9/12/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/8/2006 | | DONE |
|
|
|
Plan taken to front desk ready for issue.
|
Permit Ready to Issue | | | 9/8/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/8/2006 | | 9/8/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/8/2006 | | DONE |
|
|
|
left vm/###-####/told permit was ready, project name & address, and fee
|
Plan resubmittals received | | | 8/17/2006 | | DONE |
|
|
|
|
Alarm Plan Check | 7/31/2006 | | 7/26/2006 | | FAIL |
|
|
|
Plans reviewed 7/16/06 by FV; subsequently disapproved by MF/SLR due to inadequate notification devices/partial coverage. Vangauard (vendor) advised by phone by MF. Vangaurd picked up one set for reference for revision. Will resubmit.
|
Miscellaneous action | | | 7/11/2006 | | |
|
|
|
Sent to Floyd Varley
|
Application received | | | 7/7/2006 | | |
|
|
|
|
Case Summary | | | 7/7/2006 | | DONE |
|
|
|
|
INSP-Final Inspection | 2/22/2007 | 2/23/2007 | | A | |
|
|
|
KEITH ###-####
|
Alarm Plan Check | 9/8/2006 | | | | PASS |
|
|
|
Resubmittal review found to be acceptable see FA Review comments.
|