Permit Information
Permit NumberFIR06-00502
StatusFinaled
Name GENERAL FIRE INC
Site Address 6455 S EISENMAN RD
Project NameHarris Auto Sales Facility
Customer Number 
ePlanReview 
Description
To provide a required sprinkler monitoring system in new building.

The associated building permit (BLD 06-01011) is to Harris Auto Sales Facility - To construct a 6,210 sq. ft. two story type VB fully fire sprinklered auto sales facility with maintenance shop and wash bay. Other work includes all site improvements paving and landscaping per approved attachments, CUP05-00017, DRH05-00047. 1st floor 2768 sq.ft., 2nd floor 3442 sq. ft., fire sprinklers used for story increase
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/2/200611/2/200611/2/2006PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Final Inspection11/2/200611/2/200611/2/2006APART
DetailsForrest France
Two of three items on the previous correction notice have been verified for completion including signage at the door to the FACP room and retest of the PIV tamper switch. The latching supervisory signals at the panel have been conditionally accetped for this project only by Boise City PDS department head B. Chatterton. Contractor failed to produce NFPA 72 record of completion forms at final testing, permit final pending correct documentation for acceptance signature.
INSP-Alarm Testing10/31/200610/31/200611/1/2006PNR
DetailsForrest France
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
INSP-Alarm Testing10/24/200610/25/200610/25/2006PFAIL
DetailsForrest France
The PIV tamper switch is not adjusted accurately, supervisory tamper switches shall be non-latching per requirements, need to provide a sign at the door to the room containing the FACP per review note #16.
Issue and Print Permit  8/9/2006 DONE
Permit Ready to Issue  8/8/2006 DONE
Inspection Record Card- Fire8/8/2006 8/8/2006 DONE
Telephone call  8/8/2006 DONE
spoke to lorna@###-####/told permit was ready, permit#, project name & address, and fee
Alarm Plan Check8/7/2006 8/7/2006 PASS
Resubmittal acceptable.
PLANS/APPL TAKEN TO FRONT DESK  8/7/2006 DONE
Plan resubmittals received  7/25/2006  
Alarm Plan Check  7/21/2006 DONE
Resubmittal is required. Faxed comments to Mike Fease.
Telephone call  7/20/2006 DONE
Received an incomplete application. Phoned Mike Fease to request the BLDG owner name and contact numbers and the installers name and contact numbers. I told him he could fax the front sheet of the application to ###-####.
Case Summary  7/10/2006  
Application received  7/10/2006  
Plan assigned to (Mary)7/10/2006