INSP-Final Inspection | 11/30/2007 | 12/3/2007 | 12/3/2007 | A | PASS |
Forrest France
|
|
|
Required corrections have been made, final inspection passed, shell and core fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 | A | PART |
Forrest France
|
|
|
Items on correction notice are complete with the exception of four missing DP heads, need to provide coverage for an open space at the 1st floor or completely enclose as indicated on the building plans to create a non-combustible concealed space, repair the flow switch at the pump discharge manifold, ceiling tiles at some locations are still missing.
|
INSP-Final Inspection | 11/28/2007 | 11/29/2007 | 11/29/2007 | A | FAIL |
Forrest France
|
|
|
Red lined areas on approved plan set in need of revision including covered heads, painted heads, missing heads at two locations, incorrect spacing, need to certify the RP and DC valves, perform forward flow, provide signage at floor control vavles, missing ceiling tile and escutcheons at some areas.
|
INSP-Final Inspection | 11/27/2007 | 11/28/2007 | 11/28/2007 | A | NR |
Forrest France
|
|
|
|
INSP-Final Inspection | 11/26/2007 | 11/27/2007 | 11/27/2007 | P | CANC |
Forrest France
|
|
|
Overbooked
|
INSP-Final Inspection | 11/21/2007 | 11/26/2007 | 11/26/2007 | A | PART |
Forrest France
|
|
|
Completed sprinkler monitoring testing including the dry system, fire pump, controller and power supplies, noted a QOD is not required on the dry system, missing coverage at the stairs to the basement electrical room, need signage at valves, missing head boxes, finish pack, need to complete forward flow of the BFP, also need to complete a final shell system walkthrough.
|
INSP-Final Inspection | 11/20/2007 | 11/21/2007 | 11/23/2007 | A | PART |
Forrest France
|
|
|
Begin testing for sprinkler monitoring including tampers and flows at floor control valves, noted one incorrect device address.
|
INSP-Final Inspection | 11/19/2007 | 11/20/2007 | 11/20/2007 | P | NR |
Forrest France
|
|
|
|
INSP-Conference | 10/26/2007 | 10/31/2007 | 11/1/2007 | P | PART |
Forrest France
|
|
|
Completed preliminary fire pump testing including the required min. manual and automatic starts/stops, churn, rated and peak load testing, and flow testing for comparison to mfg. performance curve data. Generator is not completed to enable testing of the transfer switch at the controler, no fire alarm interconnection or supervision tested at this time due to incomplete FA work.
|
INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 | P | PART |
Forrest France
|
|
|
Conclusion of the 24 hr air test for the dry system passed within allowable pressure loss, corrections completed as noted for the common corridors on the 3rd-6th floors.
|
INSP-Sprinkler Rough-in | 10/26/2007 | 10/29/2007 | 10/29/2007 | P | PART |
Forrest France
|
|
|
Begin 24 hr. air test for the dry system at 45 psig. at 3:45 pm.
|
INSP-Sprinkler Rough-in | 10/25/2007 | 10/26/2007 | 10/29/2007 | P | FAIL |
Forrest France
|
|
|
Duplicated inspection request already completed.
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 | P | FAIL |
Forrest France
|
|
|
Inspection for the OH rough-in at the common corridors on the 3rd thru 6th floors failed due to overspaced hangers at arm-overs, uprights need to be installed at mech/equip. rooms, incorrect head spacing at the 6th floor, noted sensing lines at the FP and JP are not correct per NFPA 20. The OH hydrostatic test passed.
|
INSP-Sprinkler Rough-in | 8/16/2007 | 8/17/2007 | 8/17/2007 | A | PART |
Forrest France
|
|
|
1st floor dry system at the NE covered parking area is approved for cover, noted installer to maintain spacing per design not to exceed 120ft sq.
|
INSP-Sprinkler Rough-in | 6/11/2007 | 6/12/2007 | 6/13/2007 | A | PART |
Forrest France
|
|
|
4th, 5th and 6th floor overhead rough-in inspection passed, missing two seismic braces on the 6th floor, also noted head spacing to be adjusted due to tenant walls.
|
INSP-Sprinkler Rough-in | 6/8/2007 | 6/11/2007 | 6/11/2007 | A | PART |
Forrest France
|
|
|
OH rough-in for the dry system passed inspection, noted one missing seismic brace at the last piece of 3" main on the 1st floor, OH rough-in for the 3rd floor also completed including terraces, noted some wall changes within the suite spaces which will require some head spacing location mods.
|
INSP-Sprinkler Rough-in | 6/7/2007 | 6/8/2007 | 6/8/2007 | A | CANC |
Forrest France
|
|
|
rough in for 2nd - 6th floors Jonathon is the contact Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|
INSP-Sprinkler Rough-in | 4/25/2007 | 4/27/2007 | 4/27/2007 | P | FAIL |
Forrest France
|
|
|
Inspection for the terrace portions of the 3rd and 4th floor failed due to overspaced heads, missing heads and lines which need to be reconfigured as discussed.
|
INSP-Sprinkler Rough-in | 2/21/2007 | 2/22/2007 | 2/22/2007 | A | CANC |
Forrest France
|
|
|
This is an overhead rough in for the 3rd and 4th floors. Contact is Jonathon @###-####. Thank You! Phone #: ###-#### Cancel inspection per phone call from contractor.
|
INSP-Sprinkler Rough-in | 2/15/2007 | 2/15/2007 | 2/16/2007 | P | PART |
Forrest France
|
|
|
The OH piping hangers and seismic attatchments are okay for cover at the penthouse area only.
|
INSP-Conference | 1/11/2007 | 1/16/2007 | 1/16/2007 | A | DONE |
Forrest France
|
|
|
On site conference to discuss fire related HVAC issues.
|
Issue and Print Permit | | | 12/27/2006 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/26/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/26/2006 | | 12/26/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/26/2006 | | |
|
|
|
tlk to lilly ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 12/26/2006 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/10/2006 | | 12/26/2006 | | PASS |
|
|
|
12/26/2006 11:09:44 SMBT - activity updated through activity FIRA22 from case FIR06-00504.
|
Sprinkler Plan Check | 12/14/2006 | | 12/22/2006 | | PASS |
|
|
|
Plan review by Bryan Johnson
|
Plan resubmittals received | | | 12/14/2006 | | |
|
|
|
|
Sprinkler Plan Check | 11/21/2006 | | 11/30/2006 | | FAIL |
|
|
|
B. Johnson reviewed plans and emailed comments to applicant.
|
Plan resubmittals received | | | 11/21/2006 | | |
|
|
|
|
Miscellaneous action | | | 10/5/2006 | | |
|
|
|
picked up failed plans
|
Sprinkler Plan Check | | | 8/12/2006 | | FAIL |
|
|
|
Reviewed by B. Johnson; review comments faxed to Shilo.
|
Application received | | | 7/10/2006 | | |
|
|
|
|