INSP-Final Inspection | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
CHANGE STATUS TO (ISS) | | | 8/14/2006 | | DONE |
|
|
|
changed by troy cobbley
|
INSP-Final Inspection | 8/10/2006 | 8/10/2006 | 8/10/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 8/8/2006 | 8/9/2006 | 8/9/2006 | A | FAIL |
Troy Cobbley
|
|
|
No testing performed since the pulls stations had been mounted too high. Candella's for the strobes was incorrect but Tony corrected it as I waited.
|
Miscellaneous action | | | 7/24/2006 | | DONE |
|
|
|
Copy of email directive from D. Hanneman to not require smokes at this time.
">>> Dave Hanneman 7/18/2006 4:28 PM >>>
Mary, Go with existing code.
Dave
>>> Mary Froemke 07/18/2006 3:45:07 PM >>>
Dave,
I'm glad to see the additional coverage in the future. For this daycare though, do you want me to follow existing code (no smokes?), or do you want to talk with them and possibly suggest placing smokes in the space (3 additional smoke detectors are required) since the new ordinance will require them?
Mary
>>> Dave Hanneman 7/18/2006 3:27 PM >>>
Mary, In the new proposed ordinance we added smokes to this type of occupancy. I think we ended up beefing up the E over and above what the code requires.
Dave
>>> Mary Froemke 07/18/2006 2:53:54 PM >>>
Hi Dave,
I have a relocatable (1949 sq ft) to be installed at St Als (6520 Norwood Dr.), the occupancy is E/50, but the building scope (BLD04-02856) indicates a daycare.
I have received fire alarm plans for a manual FA system, but have a concern that there is no smoke detector coverage. (one for the FACP only). As I haven't run into this before (Boise schools always installs smokes), I double checked IFC 2000 and for an E none are required. I spoke with Jenifer and she told me to e-mail you as the new day care ordinance is being modified and will include the smokes. If you feel that smokes would be warranted here, Jenifer thought you could call them to let them know.
Thanks for your time, please let me know how you want to roceed. Mary"
|
Permit Ready to Issue | | | 7/20/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/20/2006 | | 7/20/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/20/2006 | | DONE |
|
|
|
spoke to lisa@###-####/told permit was eady, permit#, project name & address, and no fees
|
Issue and Print Permit | | | 7/20/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 7/10/2006 | | 7/19/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 7/19/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/19/2006 | | DONE |
|
|
|
|
Telephone call | | | 7/18/2006 | | DONE |
|
|
|
Phoned Jason Minnick; require FACP battery charging capacity and max battery size and smoke detector compatibility listing.
|
Application received | | | 7/10/2006 | | |
|
|
|
|
Reinspection Fee (no hold) | 8/10/2006 | 8/10/2006 | | P | |
Troy Cobbley
|
|
|
Please Call 1-hour before for the time that you can inspect. Call Ken at ###-#### Thank You.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick
|