Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR06-00506
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 6444 W NORWOOD DR
Project Namealm SARMC * Early Learning Cen
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system in the new modular building.

The building permit BLD04-02856 is to place one 1949 sq. ft. one story modular daycare building with new accessible ramps and stairs, interior remodel and additional site work. Add foundation piers, tie downs, skirting, new concrete sidewalks, electrical and plumbing. All per approved plans DRH 04-00175 Mod #1 CUP04-00081 Tag #4288CC SARMC * Early Learning Center *
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/22/20069/22/20069/22/2006PPASS
DetailsTroy Cobbley
permit finaled
CHANGE STATUS TO (ISS)  8/14/2006 DONE
changed by troy cobbley
INSP-Final Inspection8/10/20068/10/20068/10/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection8/8/20068/9/20068/9/2006AFAIL
DetailsTroy Cobbley
No testing performed since the pulls stations had been mounted too high. Candella's for the strobes was incorrect but Tony corrected it as I waited.
Miscellaneous action  7/24/2006 DONE
Copy of email directive from D. Hanneman to not require smokes at this time.
">>> Dave Hanneman 7/18/2006 4:28 PM >>>
Mary, Go with existing code.
Dave
>>> Mary Froemke 07/18/2006 3:45:07 PM >>>
Dave,
I'm glad to see the additional coverage in the future. For this daycare though, do you want me to follow existing code (no smokes?), or do you want to talk with them and possibly suggest placing smokes in the space (3 additional smoke detectors are required) since the new ordinance will require them?
Mary
>>> Dave Hanneman 7/18/2006 3:27 PM >>>
Mary, In the new proposed ordinance we added smokes to this type of occupancy. I think we ended up beefing up the E over and above what the code requires.
Dave
>>> Mary Froemke 07/18/2006 2:53:54 PM >>>
Hi Dave,
I have a relocatable (1949 sq ft) to be installed at St Als (6520 Norwood Dr.), the occupancy is E/50, but the building scope (BLD04-02856) indicates a daycare.
I have received fire alarm plans for a manual FA system, but have a concern that there is no smoke detector coverage. (one for the FACP only). As I haven't run into this before (Boise schools always installs smokes), I double checked IFC 2000 and for an E none are required. I spoke with Jenifer and she told me to e-mail you as the new day care ordinance is being modified and will include the smokes. If you feel that smokes would be warranted here, Jenifer thought you could call them to let them know.
Thanks for your time, please let me know how you want to roceed. Mary"
Permit Ready to Issue  7/20/2006 DONE
Inspection Record Card- Fire7/20/2006 7/20/2006 DONE
Telephone call  7/20/2006 DONE
spoke to lisa@###-####/told permit was eady, permit#, project name & address, and no fees
Issue and Print Permit  7/20/2006  
Plan assigned to (Mary)7/10/2006 7/19/2006 DONE
Alarm Plan Check  7/19/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  7/19/2006 DONE
Telephone call  7/18/2006 DONE
Phoned Jason Minnick; require FACP battery charging capacity and max battery size and smoke detector compatibility listing.
Application received  7/10/2006  
Reinspection Fee (no hold)8/10/20068/10/2006 P 
DetailsTroy Cobbley
Please Call 1-hour before for the time that you can inspect. Call Ken at ###-#### Thank You.; Phone #: ###-#### Internet Inspection Request from: Jason Minnick