Permit Information
Permit NumberFIR06-00507
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 9050 W OVERLAND RD
Project NameBLACKEAGLE BLDG
Customer Number 
ePlanReview 
Description
Installation of sprinkler monitoring, elevator recall and notification devices in core areas of shell building.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/6/200611/7/200611/7/2006APASS
DetailsForrest France
Final shell fire alarm inspeciton passed, permit finaled.
INSP-Final Inspection11/3/200611/6/200611/7/2006AFAIL
DetailsForrest France
Initial inspection failed due to latching supervisory signals at the panel.
INSP-Final Inspection11/2/200611/3/200611/3/2006ACANC
DetailsForrest France
No time available to complete this inspection.
INSP-Final Inspection11/2/200611/6/200611/2/2006ACANC
DetailsTroy Cobbley
Call us when you have a time. Thanks; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
INSP-Final Inspection11/1/200611/2/200611/2/2006ANR
DetailsForrest France
Per contractor the elevator shaft smoke and heat detectors are not yet installed.
Telephone call  11/2/2006 DONE
gave plans to customer
Plan resubmittals received  11/1/2006  
Override - Parcel Holds  9/21/2006  
Issue and Print Permit  9/21/2006 DONE
Telephone call  9/20/2006 DONE
left mess that permit is ready
PLANS/APPL TAKEN TO FRONT DESK  8/15/2006 DONE
Override - Parcel Holds  8/15/2006  
Permit Ready to Issue  8/15/2006 DONE
Override - Parcel Holds  8/15/2006  
Inspection Record Card- Fire8/15/2006 8/15/2006 DONE
Telephone call  8/15/2006 DONE
spoke to robin@###-####/told permit was ready, permit#, project name & address, and fee
Alarm Plan Check  8/11/2006 PASS
Resubmittal reviewed by F. Varley, no review comments.
Alarm Plan Check  7/18/2006 FAIL
Resubmittal is required.

1) The building permit must be issued prior to a resubmittal accepted.

2) The 2nd floor of the building consists of ~ 16,000 sq feet, the bulding permit is for a "B" and "M" occupancy within the building. Therefore, for a "B" and "M", a manual fire alarm system is required for more than 100 persons above or below the lowest level of exit discharge.
Application received  7/10/2006  
Plan assigned to (Mary)7/10/2006