INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | PASS |
Forrest France
|
|
|
Final shell fire alarm inspeciton passed, permit finaled.
|
INSP-Final Inspection | 11/3/2006 | 11/6/2006 | 11/7/2006 | A | FAIL |
Forrest France
|
|
|
Initial inspection failed due to latching supervisory signals at the panel.
|
INSP-Final Inspection | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | CANC |
Forrest France
|
|
|
No time available to complete this inspection.
|
INSP-Final Inspection | 11/2/2006 | 11/6/2006 | 11/2/2006 | A | CANC |
Troy Cobbley
|
|
|
Call us when you have a time. Thanks; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 | A | NR |
Forrest France
|
|
|
Per contractor the elevator shaft smoke and heat detectors are not yet installed.
|
Telephone call | | | 11/2/2006 | | DONE |
|
|
|
gave plans to customer
|
Plan resubmittals received | | | 11/1/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 9/21/2006 | | |
|
|
|
|
Issue and Print Permit | | | 9/21/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/20/2006 | | DONE |
|
|
|
left mess that permit is ready
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/15/2006 | | |
|
|
|
|
Permit Ready to Issue | | | 8/15/2006 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/15/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 8/15/2006 | | 8/15/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2006 | | DONE |
|
|
|
spoke to robin@###-####/told permit was ready, permit#, project name & address, and fee
|
Alarm Plan Check | | | 8/11/2006 | | PASS |
|
|
|
Resubmittal reviewed by F. Varley, no review comments.
|
Alarm Plan Check | | | 7/18/2006 | | FAIL |
|
|
|
Resubmittal is required.
1) The building permit must be issued prior to a resubmittal accepted.
2) The 2nd floor of the building consists of ~ 16,000 sq feet, the bulding permit is for a "B" and "M" occupancy within the building. Therefore, for a "B" and "M", a manual fire alarm system is required for more than 100 persons above or below the lowest level of exit discharge.
|
Application received | | | 7/10/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 7/10/2006 | | | | |
|
|
|
|