Permit Information
Permit NumberFIR06-00511
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 950 W BANNOCK ST
Project Name10TH & BANNOCK-9TH FLR
Customer Number 
ePlanReview 
Description
GREENER BANDUCCI SHOEMAKER - BANNER BANK - STE 900) This building is fire sprinklered because it is a high-rise. To construct an 12,200 square foot office tenant space on the 9th story of a high-rise building. Work is to include 1-hr corridor walls, smoke- and draft-control doors with wire glass sidelights in 1-hr corridor walls, interior Nordwall demountable nonbearing partitions with doors and sidelights, millwork, and finishes. The access floor system and the suspended ceilings were installed under permit BLD05-02939. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/16/200610/16/200610/16/2006PPASS
DetailsForrest France
Items on previous correction notice have been verified for completion, one remaining overspaced head relocated while on site, final inspection passed, permit finaled.
INSP-Final Inspection10/13/200610/13/200610/13/2006PFAIL
DetailsForrest France
Heads in the file storage room are overspaced, two heads at the reception area on the north side are overspaced off an adjacent wall, one head in a south office as marked on plans needs to be relocated for proper coverage, inspected relocated heads outside the scope of work in the elevator lobby and 1hr corridors, some field modifications have been made which are not included on approved plans.
INSP-Sprinkler Rough-in/Hydro9/18/20069/19/20069/19/2006APART
DetailsForrest France
Sprinkler rough-in at the hard lid areas in the elevator lobby and south reception area are good for cover.
Issue and Print Permit  9/12/2006 DONE
Plan assigned to (Bill)7/12/2006 9/11/2006 DONE
No plan review attached electronically. plans outsourced for review.
Sprinkler Plan Check9/11/2006 9/11/2006 PASS
Plans reviewed by Bryan Johnson.
PLANS/APPL TAKEN TO FRONT DESK  9/11/2006  
Permit Ready to Issue  9/11/2006 DONE
Inspection Record Card- Fire9/11/2006 9/11/2006 DONE
Telephone call  9/11/2006 DONE
left vm for Gerald@###-####/told permit was ready, permit#, project name, and fees
Plan resubmittals received  8/17/2006  
Application received  7/12/2006  
Case Summary  7/12/2006 DONE