Permit Information
Permit NumberFIR06-00516
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 671 E RIVERPARK LN
Project NameRIVER RUN BLDG F
Customer Number 
ePlanReview 
Description
To remove the existing non-required and non-compliant fire alarm system and install a new elevator recall system. The existing system is a non-required system consisting of four manual pull stations and four horns. The building is not sprinklered, is a B occupancy, and has an occupant load of less than 100 on the second floor. The occupant load information was provided by Mary Froemke. The existing devices are located at the top of the stairwells and at the main floor exits.

The associated building permit (BLD06-00731) is the interior remodel to upgrade the building core restrooms on the first and second floor, to install a new elevator within a one-hour rated elevator shaft, and construct a one-hour rated elevator equipment room in an existing two story building per approved plans. Work to include some miscellaneous interior demolition work, some new one-hour rated corridor walls, some new 20 minute rated corridor doors, new one-hour rated elevator shaft walls and ceiling, new smoke door at elevator opening on first floor, some structural work to existing structure to accommodate new elevator shaft, new concrete elevator pit, other new interior walls, interior finish, some minor suspended ceiling and soffit work, fire alarm work, mechanical work, plumbing work, and electrical work. This permit is attached to the same set of plans along with another permit for work being done under BLD06-00730 in an adjacent building on the site. This is a Scope of Work Permit. A Letter of Completion is to be issued when done. This building is now called River Run Center Bldg. F. (It was formerly called Bldg. B.) NOTE: This building currently has a one-hour rated corridor on the first floor that extends up to the top of the stairways. The second floor currently has a non-rated hallway. The architect will provide one-hour rated walls and 20 minute rated doors at the restrooms on the second floor in case a future one-hour corridor is constructed on this second floor. NOTE: This building is not fire sprinklered. JCB
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/9/200610/9/200610/9/2006PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing10/5/200610/9/200610/9/2006APASS
DetailsForrest France
Items required for final have been verified for completion, inspection passed.
INSP-Final Inspection10/4/200610/4/200610/5/2006PCANC
DetailsTroy Cobbley
waiting for Forrest to verify as-builts or for the contractor to walk me throught the system to verify it myself
INSP-Alarm Testing10/3/200610/3/200610/3/2006PPART
DetailsForrest France
Panel and devices tested okay, need to provide signage at the door and as-built plans reflecting field modifications and actual installation.
Issue and Print Permit  8/4/2006 DONE
Plan assigned to (Mary)7/13/2006 7/27/2006 DONE
Alarm Plan Check7/13/2006 7/27/2006 PASS
DetailsTroy Cobbley
PLANS/APPL TAKEN TO FRONT DESK  7/27/2006 DONE
Permit Ready to Issue  7/27/2006 DONE
Inspection Record Card- Fire7/27/2006 7/27/2006 DONE
Telephone call  7/27/2006 DONE
spoke to sharon@###-####/told permit was ready, permit#, address, project name, and fee
Case Summary  7/13/2006 DONE
Application received  7/13/2006