Permit Information
Permit NumberFIR06-00518
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 4705 W EMERALD ST
Project NameBoise Foreign Auto
Customer Number 
ePlanReview 
Description
Beginning from an existing UG stub up into the bldg., install a new wet electric riser & wet pipe system to serve through out the existing 6,100 ft/2 heated bldg. The Underground supply was installed and accepted under permit # FIR04-00610. This permit is attached to BLD04-00084.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
Original Scope of Work:
Beginning from an existing UG stub up into the bldg., install a new wet electric riser & wet pipe system to serve through out the existing 10,000 ft/2 heated bldg. The Underground supply was installed and accepted under permit # FIR04-00610. This permit is attached to BLD04-00084.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code.
(03/22/07)
It appears that five upright heads were added in the remote area at the upper level. These heads need to be added to the calculations. Please resubmit plans and calculations to support this modification.
065/26/07 The heads were added to the calculations.
06/26/07 Rev #7 Revised Scope of Work:
Changes to the piping arrangement in the remote area were made during construction resulting in a resubmittal of plans and calculations.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/11/20077/12/20077/12/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/10/20077/11/20077/11/2007PFAIL
DetailsTroy Cobbley
The fire dept connection is mounted too high and not all of the ceiling tile has been installed. The forward flush passed.
Issue and Print Permit  7/3/2007 DONE
Sprinkler Plan Check6/26/2007 7/2/2007 PASS
Plans are approved by Bryan Johson
PLANS/APPL TAKEN TO FRONT DESK  7/2/2007 DONE
Inspection Record Card- Fire7/2/2007 7/2/2007 DONE
Telephone call  7/2/2007 DONE
lft ms for john ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  7/2/2007 DONE
Plan resubmittals received  3/15/2007 DONE
received three copies of sheets FP-1 FP-2 sprinkler data, calculations and bracing placed plans in bin for pickup.rad
Plan assigned to (SAM)3/15/2007 3/15/2007 DONE
INSP-Sprinkler Rough-in/Hydro2/15/20072/15/20072/15/2007PPASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Sprinkler Rough-in/Hydro2/14/20072/14/20072/14/2007PPASS
DetailsTroy Cobbley
underground hydro test passed
INSP-Supply line flush2/8/20072/9/20072/9/2007PPASS
DetailsTroy Cobbley
Underground flush passed.
Issue and Print Permit  11/15/2006 DONE
Inspection Record Card- Fire10/26/2006 10/26/2006 DONE
Telephone call  10/26/2006  
lft ms for tim fleming ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  10/26/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/25/2006 DONE
Plan assigned to (Bill)7/14/2006 10/25/2006 PASS
10/25/2006 16:23:36 SLR - activity updated through activity FIRA22 from case FIR06-00518.
Sprinkler Plan Check  10/20/2006 PASS
3rd revision approved subject to comments, by B. Johnson.
Telephone call  10/5/2006  
Faxed Copy of Denied Review to Applicant
Sprinkler Plan Check  9/30/2006 FAIL
Plans review by Brian Johnson Failed 9/30/06
Plan resubmittals received  9/15/2006  
Sprinkler Plan Check  9/12/2006 FAIL
Resubmittal reviewed and denied by B. Johnson. Hyd. cover sheets and summary reports do not correspond with each other and also do not correspond with the plans FP-2 hyd. placard. Review comments faxed to Commercial Fire.
Plan resubmittals received  8/29/2006  
Sprinkler Plan Check  8/8/2006 FAIL
Plans reviewed by BJ; denied. One set taken to front counter for pickup by contracotr.
Application received  7/14/2006  
Case Summary  7/14/2006 DONE