INSP-Final Inspection | 12/20/2006 | 12/20/2006 | 12/20/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 11/13/2006 | 11/16/2006 | 11/16/2006 | A | FAIL |
Forrest France
|
|
|
Pendent head in office 305 is overspaced off an adjacent wall, head in the mechanical closet is partially blocked and installed too close to adjacent ductwork.
|
Plan assigned to (Bill) | 7/19/2006 | | 10/4/2006 | | PASS |
|
|
|
10/4/2006 15:45:38 MWT - activity updated through activity FIRA22 from case FIR06-00757.
|
Telephone call | | | 8/18/2006 | | DONE |
|
|
|
spoke to liz@###-####/told permit was ready, permit#, project name & address, and fee
|
Issue and Print Permit | | | 8/18/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/13/2006 | | 8/17/2006 | | PASS |
|
|
|
Approved by B. Johnson per attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/17/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/17/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/17/2006 | | 8/17/2006 | | DONE |
|
|
|
|
Case Summary | | | 7/19/2006 | | DONE |
|
|
|
|
Application received | | | 7/19/2006 | | |
|
|
|
|