INSP-Final Inspection | 9/29/2006 | 10/2/2006 | 10/2/2006 | A | PASS |
Forrest France
|
|
|
Fire alarm corrections have been verified for completion, inspection passed, permit finaled.
|
INSP-Final Inspection | 9/22/2006 | 9/25/2006 | 9/25/2006 | A | PART |
Forrest France
|
|
|
Need to install a SD and HD at the top of the elevator hoistway per plan, also need to provide as-builts reflecting field modifications. Remaining fire alarm tested satisfactory.
|
INSP-Alarm Testing | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | PART |
Forrest France
|
|
|
Reinspection for c/n items related to the 2nd floor fire alarm tested satisfactory, signals verified. The 1st floor alarm, elevator, updated map, and EOL,s are not completed for inspection at this time.
|
INSP-Alarm Testing | 8/14/2006 | 8/15/2006 | 8/15/2006 | P | FAIL |
Forrest France
|
|
|
Three duct detectors are incorrectly installed, wall mounted av in the electrical room appears to be a ceiling only av, partial test only of the 2nd floor completed today.
|
Permit Ready to Issue | | | 8/7/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/7/2006 | | 8/7/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/7/2006 | | DONE |
|
|
|
spoke to charlie@###-####/told permit was ready, permit#, project name & address, and fee
|
Issue and Print Permit | | | 8/7/2006 | | |
|
|
|
|
Alarm Plan Check | | | 8/4/2006 | | PASS |
|
|
|
Approved by FV subject to attached comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/4/2006 | | DONE |
|
|
|
|
Application received | | | 7/20/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 7/20/2006 | | | | |
|
|
|
|
Plan assigned to (SAM) | 7/28/2006 | | | | |
|
|
|
plans mailed to FV.
|