INSP-Final Inspection | 8/28/2006 | 8/28/2006 | 8/29/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 8/28/2006 | 8/28/2006 | 8/28/2006 | P | PASS |
Forrest France
|
|
|
Corrections have been made, inspection passed, signals recieved to be faxed for verification.
|
INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | FAIL |
Forrest France
|
|
|
Both manual pull stations are installed above max. height allowed AFF, the H/S and manual pulls installed do not match submittals (different manufacturers).
|
Issue and Print Permit | | | 8/16/2006 | | DONE |
|
|
|
|
Alarm Plan Check | 8/3/2006 | | 8/15/2006 | | PASS |
|
|
|
Approved with no review comments. Plans sent to FV 8/3/2007 for review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/15/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/15/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/15/2006 | | DONE |
|
|
|
spoke to john@###-####/told permit was ready, permit#, project name & address, and fee
|
Inspection Record Card- Fire | 8/15/2006 | | 8/15/2006 | | DONE |
|
|
|
|
Application received | | | 7/27/2006 | | |
|
|
|
|