Permit NumberFIR06-00558
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameST LUKES
Customer Number 
ePlanReview 
Description
Modify the existing wet pipe system by installing 174 new Quick Response pendants
to accommodate a new ceiling layout to the North & East of the Ground floor. The heads will be supplied from existing 1" outlets and or 1" mechanical tees. This remodel spans approximately 16,000 sq.ft. of I-2 hospital exam rooms, surgery & support areas to prepare for construction of three new operating rooms with surgery waiting and POHA suite with administrative support areas. Work includes selective interior demolition; new interior, non-combustible walls to create exit access path to serve all areas, to divide specialized service suites and rooms; add new interior finishes, cabinetry and specialized equipment; maintain integrity of 2-hour floor & shaft assemblies and 1-hour smoke barrier walls and construct new 1-hour incidental use walls. Separate applications and permits are required for modifications to the alarm systems, as regulated by the fire department.
This permit is attached to BLD06-01392.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/18/20075/18/20075/18/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in3/29/20073/30/20073/30/2007APART
DetailsForrest France
The OH install at the drop ceilings in the hallway adjacent to the OR rooms are approved for cover, one head to be added for complete coverage of the pockets along the corridor as discussed, see plans for areas inspected to date.
INSP-Sprinkler Rough-in3/2/20073/5/20073/5/2007APART
DetailsForrest France
OH fire sprinkler rough-in as noted on approved plan set is acceptable for cover, c/n items from previous inspection of this area are complete.
INSP-Sprinkler Rough-in2/26/20072/26/20072/26/2007PPART
DetailsForrest France
OH rough-in is okay for cover at the areas and rooms as circled on approved plans, noted two missing heads in OR17, one damaged head in the corridor, and possible obstruction issues by the curtain track at some patient rooms.
INSP-Sprinkler Rough-in1/30/20071/31/20071/31/2007APART
DetailsForrest France
OH sprinkler rough-in at the drop ceilings in area A as marked on approved plan set are okay to cover. Noted two overspaced heads in the play area to be relocated, also noted three heads as circled on plans are not yet completed.
INSP-Sprinkler Rough-in11/17/200611/17/200611/17/2006PPART
DetailsForrest France
Sprinkler rough-in for cover at the hard lid ceilings in area A as circled and initialed on approved plan set are good for cover.
INSP-Final Inspection11/7/200611/8/200611/8/2006APART
DetailsForrest France
Fire sprinkler at the waiting area only as previously inspected is acceptable.
INSP-Sprinkler Rough-in10/19/200610/20/200610/20/2006APART
DetailsForrest France
OH rough in at the ground floor section A surgery waiting is okay to cover except one area as circled on approved plans which is overspaced.
Issue and Print Permit  8/22/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/21/2006 DONE
Permit Ready to Issue  8/21/2006 DONE
Inspection Record Card- Fire8/21/2006 8/21/2006 DONE
Telephone call  8/21/2006 DONE
spoke to crystal@###-####/told permit was ready, permit#, project, and fee
Sprinkler Plan Check  8/18/2006 PASS
Reviewed by B. Johnson
Application received  7/28/2006  
Plan assigned to (Bill)7/28/2006