Permit NumberFIR06-00564
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 1001 S ORCHARD ST
Project NameAgape Christian Worship Ctr
Customer Number 
ePlanReview 
Description
This building is required to be fire sprinkled for area increase. This existing 15,158 square foot office building will be converted into a church. The assembly room will have a floor area of about 3,626 square feet and an occupant load of 281. The occupant load is limited by fixed seats. Work is to include interior nonbearing walls, interior doors, interior windows, and a platform. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Install new wet system in existing building in warm occupied areas. Install new dry system in unheated attic.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-01803.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference1/8/20071/9/20071/9/2007ADONE
DetailsTroy Cobbley
I went over life safety issues with John. Exit discharge lighting will be required and the two doors behind the platform can remain as long as all hardware is removed and the doors are covered/blocked from view.
INSP-Sprinkler Rough-in/Hydro1/3/20071/3/20071/3/2007PPASS
DetailsTroy Cobbley
Above ground hydro test of the wet and dry system passed. It took two trys for the dry system.
INSP-Supply line flush12/29/200612/29/200612/29/2006APASS
DetailsTroy Cobbley
Underground hydro and flush is passed. Overhead wet system rough-in is passed.
INSP-Supply line flush12/14/200612/14/200612/14/2006APASS
DetailsTroy Cobbley
Underground supply piping is ok to cover. I notified the fire sprinkler contractor that the PIV will be required to be electronically supervised and that it would be a good idea to install the conduit in the open trench prior to bury.
INSP-Sprinkler Rough-in/Hydro11/20/200611/21/200611/21/2006APASS
DetailsTroy Cobbley
24 hour air test on the dry system passed
INSP-Sprinkler Rough-in/Hydro11/20/200611/20/200611/20/2006APASS
DetailsTroy Cobbley
dry system is ok to cover. The single head in the overbuild area needs relocated. See approved plans for location
Issue permit  8/31/2006 DONE
Permit Ready to Issue  8/30/2006 DONE
Inspection Record Card- Fire8/30/2006 8/30/2006 DONE
Telephone call  8/30/2006 DONE
left vm@###-####/told permit was ready, permit#, project name & address, and fees
PLANS/APPL TAKEN TO FRONT DESK  8/29/2006 DONE
Sprinkler Plan Check  8/28/2006 PASS
Reviewed by B. Johnson.
Application received  8/1/2006  
Plan assigned to (Bill)8/1/2006