Permit Information
Permit NumberFIR06-00570
StatusFinaled
Name PEAK ALARM
Site Address 210 N MILWAUKEE ST
Project NameCafe Ole
Customer Number 
ePlanReview 
Description
To install a new fire alarm system to provide offsite monitoring of the new fire sprinkler system and a new cooking hood extinguishing system. Plans show no change in building area, use or occupancy. No building permit has been applied for but the sprinkler plan review indicates a new riser room will be constructed and a building permit is required for the new room. 4/5/2007 2nd review by Mike Timmerman. This permit is to install an new fire alarm system due to building area increase in patio area. building is to be fully fire sprinklered and a manual fire alarm system is required
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20077/27/20077/27/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/25/20077/26/20077/26/2007ACANC
DetailsTroy Cobbley
To be rescheduled
INSP-Final Inspection7/24/20077/25/20077/25/2007AFAIL
DetailsTroy Cobbley
The phone line troubles do not report correctly. Also need to test the duct smoke detectors.
INSP-Final Inspection6/13/20076/18/20076/18/2007AFAIL
DetailsTroy Cobbley
See the city approved plans for locations where additional a/v's will be required to be installed. These areas were in question on the reviewed plans. Candella needs to be changed on several of the a/v's as marked on the plans. Also the duct smoke detectors are not attached securely to the duct, are oriented the wrong way and have incorrect sample tube lengths. Contractor is to supply the signals as well at the next inspection.
INSP-Final Inspection5/4/20075/4/20075/4/2007PPART
DetailsTroy Cobbley
A temporary occupancy was given by dave hanniman for the new areas to be occupied while the fire alarm and fire sprinkler systems are finished being installed.
Issue and Print Permit  4/9/2007 DONE
Alarm Plan Check4/5/2007 4/5/2007 PASS
Fire Alarm Review 2nd
PLANS/APPL TAKEN TO FRONT DESK  4/5/2007  
Ready for Issue
Permit Ready to Issue  4/5/2007 DONE
Inspection Record Card- Fire4/5/2007 4/5/2007 DONE
Telephone call  4/5/2007 DONE
call to ben jackson, left msg to p/u permit, fee $ 200.40
Plan resubmittals received  4/2/2007  
Telephone call  3/20/2007  
gave plans to customer resubmittal required per mike timmerman
Alarm Plan Check8/22/2006 8/22/2006 FAIL
Plans show no change in building area, use or occupancy. No building permit has been applied for but the sprinkler plan review indicates a new riser room will be constructed and a building permit is required for the new room. Spoke with Cafe Ole Op's mgr who indicated the sprinklers were required because they "are enclosing the patios". He indicated BRS is the architect and should have submitted plans. I left a voice message for Kyle at BRS to call me. I also left a voice message with Jon Ferrin to call me to discuss the alarm design/plans. Sheet FA1 shows incorrect occupancy group (S1); need correct occupancy group and load and extent of remodel/addition work to evaluate need for manual FA system as part of this project; no sprinkler waterflow monitoring shown on floor plan or riser (just an oversight); no HVAC monitoring shown, need mechanical designer to verified that no smoke detection is required per IMC. Review comments faxed to design engineer and architect.
Case Summary  8/4/2006  
Application received  8/4/2006  
Plan assigned to (Mary)8/4/2006