Permit NumberFIR06-00571
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project NameST LUKES
Customer Number 
ePlanReview 
Description
Scope: Installation of new fire alarm system components in area of TI per upgrade agreement in 1999. Work includes new addressable smoke detectors, duct detectors, door and damper release AFS monitoring, visual notification devices and a power supply for visual signals. Existing voice/chime notification circuit remains. REF BLD06-01734
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/30/200612/1/200612/1/2006APASS
DetailsForrest France
Fire alarm work inspection passed, permit finaled.
INSP-Final Inspection11/29/200611/30/200611/30/2006AFAIL
DetailsTroy Cobbley
Showed up for inspection but found that not all of the smoke detectors had been installed. No test performed.
Issue permit  9/11/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/6/2006 DONE
Permit Ready to Issue  9/6/2006 DONE
Inspection Record Card- Fire9/6/2006 9/6/2006 DONE
Telephone call  9/6/2006 DONE
spoke to jim@###-####/told permit was ready, project name, and fee
Alarm Plan Check9/6/2006 8/31/2006 PASS
reviewed and approved without written comments by F. Varley.
Miscellaneous action  8/22/2006 DONE
plans fedexed to FV for review.
Case Summary  8/4/2006 DONE
Application received  8/4/2006  
Plan assigned to (Mary)8/4/2006