INSP-Final Inspection | 4/16/2009 | 4/16/2009 | 4/16/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 9/11/2006 | 9/11/2006 | 9/13/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit is finaled. Per John Lopez and Keith Craigen with ADT the fire dept. dispatch number has been corrected
|
INSP-Final Inspection | 9/13/2006 | 9/13/2006 | 9/13/2006 | A | PASS |
|
|
|
See notes per last inspection
|
INSP-Alarm Testing | 9/1/2006 | 9/1/2006 | 9/5/2006 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 9/1/2006 at 10:34:28 AM. Contact: ###-####. To be rescheduled per conversation with contractor.
|
INSP-Alarm Testing | 8/24/2006 | 8/25/2006 | 8/25/2006 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 8/24/2006 at 5:41:41 PM. Contact: ###-####.
|
Miscellaneous action | | | 8/25/2006 | | DONE |
|
|
|
picked up data sheets
|
Issue and Print Permit | | | 8/24/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 8/23/2006 | | |
|
|
|
|
Alarm Plan Check | 8/23/2006 | | 8/23/2006 | | PASS |
|
|
|
Resubmittal approved subject to annotations: all portable FACP monitoring signals shall be coded as Portable #1 to distinguish it from alarm signals on the main school FACP (since both are at the same street address) and a prominent sign shall be provided on the building clearly identifying it as Portable #1, which is visible from the FD access roadway. To be field verified.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/23/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/23/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/23/2006 | | 8/23/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/23/2006 | | DONE |
|
|
|
spoke to kevin@###-####/told permit was ready, permit#, project name & address, and fee
|
Alarm Plan Check | 8/22/2006 | | 8/22/2006 | | FAIL |
|
|
|
No monitoring of FACP shown on riser (i.e. no phone lines or connection to existing school FACP system). Called contractor; he indicates he did not intend to connect it to the existing school FACP but it appears the school site only has one address, so a separate FACP and monitoring for this building cannot be approved, unless an approved remote alarm annunciator is provided at the addressed main school FACP room. Advised contractor, he will pursue with the school. No review comments written at this time.
|
Application received | | | 8/4/2006 | | |
|
|
|
|