Permit NumberFIR06-00572
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 12435 W USTICK RD
Project NameUstick Elementary New Portable
Customer Number 
ePlanReview 
Description
To install a required manual fire alarm system in a new portable classroom building using a new FACP, completely separate from the existing school fire alarm system. This building is at the same address as the school but is to be separately identified and signed as Portable #1 for quick FD identification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/16/20094/16/20094/16/2009APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing9/11/20069/11/20069/13/2006PPASS
DetailsTroy Cobbley
Permit is finaled. Per John Lopez and Keith Craigen with ADT the fire dept. dispatch number has been corrected
INSP-Final Inspection9/13/20069/13/20069/13/2006APASS
See notes per last inspection
INSP-Alarm Testing9/1/20069/1/20069/5/2006PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 9/1/2006 at 10:34:28 AM. Contact: ###-####. To be rescheduled per conversation with contractor.
INSP-Alarm Testing8/24/20068/25/20068/25/2006PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/24/2006 at 5:41:41 PM. Contact: ###-####.
Miscellaneous action  8/25/2006 DONE
picked up data sheets
Issue and Print Permit  8/24/2006 DONE
Plan resubmittals received  8/23/2006  
Alarm Plan Check8/23/2006 8/23/2006 PASS
Resubmittal approved subject to annotations: all portable FACP monitoring signals shall be coded as Portable #1 to distinguish it from alarm signals on the main school FACP (since both are at the same street address) and a prominent sign shall be provided on the building clearly identifying it as Portable #1, which is visible from the FD access roadway. To be field verified.
PLANS/APPL TAKEN TO FRONT DESK  8/23/2006 DONE
Permit Ready to Issue  8/23/2006 DONE
Inspection Record Card- Fire8/23/2006 8/23/2006 DONE
Telephone call  8/23/2006 DONE
spoke to kevin@###-####/told permit was ready, permit#, project name & address, and fee
Alarm Plan Check8/22/2006 8/22/2006 FAIL
No monitoring of FACP shown on riser (i.e. no phone lines or connection to existing school FACP system). Called contractor; he indicates he did not intend to connect it to the existing school FACP but it appears the school site only has one address, so a separate FACP and monitoring for this building cannot be approved, unless an approved remote alarm annunciator is provided at the addressed main school FACP room. Advised contractor, he will pursue with the school. No review comments written at this time.
Application received  8/4/2006