Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR06-00582
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 701 E PARKCENTER BLVD
Project NameST LUKES-PRIMARY HEALTH
Customer Number 
ePlanReview 
Description
Project includes installation of a smoke detector on each side of the rear reception area door to release door hold open device upon detection of smoke, installation of new, audible/visual notification devices in the tenant improvement area to accommodate new floor plan changes. To remodel a portion of an existing 17,833 sq ft health care office space per approved plans. Work to include, selective demolition of nonbearing partitions, installation of new reception counter, installation of new one-hour fire rated door assembly, installation of suspended ceiling system and relocation of lighting, and hvac ducts and registers as required, new floor finish, miscellaneous related finishes. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. RMH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/8/20072/9/20072/8/2007APASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection1/19/20071/19/20071/23/2007AFAIL
DetailsTroy Cobbley
See entry dated 1/23/07 which still requires a map for the facp
INSP-Final Inspection1/22/20071/23/20071/23/2007AFAIL
DetailsTroy Cobbley
All items tested satifactory. A map at the facp or annunciator is all that is still required.
Issue and Print Permit  9/27/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  9/25/2006  
Ready for Issue
Permit Ready to Issue  9/25/2006 DONE
Inspection Record Card- Fire9/25/2006 9/25/2006 DONE
Telephone call  9/25/2006 DONE
spoke to charlie@###-####/told permit was ready, permit#, project name, and fee
Alarm Plan Check9/22/2006 9/22/2006 PASS
Begin Fire Alarm Review
Telephone call  9/22/2006  
Called Charlie Bayne with Simplex Grinnell asked him why a second relay base was not used on the inside smoke detector used to release door holder. Charlie explained that with the addressable fire alarm system they can activate the relay from any device programmed to activate the relay. Also asked Charlie why all initiating devices release all door holders, he explained that that is the origional building fire alarm operation as indicated on the matrix.
Plan resubmittals received  9/14/2006  
Alarm Plan Check8/22/2006 8/22/2006 FAIL
Called Simplex and Designer to clarify intent of smoke detector on each sides of door; but only one is a releasing detector and labeled "120v relay base for releasing"; while Matrix shows all DHO's release on all fire "alarm" conditions including "pump running". Not sure if this is a fire or smoke rated door. Spoke with designer, Geof Johnson, Eidam Assoc, who indicated the plans should have been routed to them for review before they were submitted to us, and agreed we should fail them. He indicated there is no fire pump so the matrix must be generic; the two detectors are provided due to the high ceiling height on the reception side, the intent was for either detector to release the door which he thinks is only a fire door. Not sure why they are using smoke detectors instead of simple fusible link releasing mechanism. No written review comments at this point. Left vm with Charlie Bayne explaining above reasons why plans were denied.
Application received  8/9/2006  
Plan assigned to (Mary)8/9/2006    
Plan assigned to (Mike)9/22/2006