INSP-Final Inspection | 11/6/2006 | 11/6/2006 | 11/7/2006 | P | PASS |
Forrest France
|
|
|
Per field inspection by M. Timmerman, fire alarm work is acceptable, inspection passed, permit finaled.
|
Inspection | 11/6/2006 | 11/6/2006 | 11/6/2006 | | PASS |
|
|
|
Fire Alarm System Inspection 11-6-2006. The fire alarm vendor provided two copies of the modified floor plan for inspection. Three pendant mount detectors were installed in front of three fire smoke dampers that have no duct work associated with them. (Thru wall only) I also checked Audio/Visual circuit for operation and performance. Fire Alarm System Passed.
|
INSP-Final Inspection | 11/2/2006 | 11/3/2006 | 11/3/2006 | P | FAIL |
Forrest France
|
|
|
Need to provide as-builts on site for field modifications not shown on approved plans, the voice evac failed to function on alarm test.
|
INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 | P | CANC |
Forrest France
|
|
|
No time to complete this inspection today, to be rescheduled per agreement with contractor.
|
Telephone call | | | 9/27/2006 | | |
|
|
|
Received a phone call from fire alarm vendor "John of Fire Sentury" John Indicated that one smoke detector would be add to this project above the ceiling. A pendant mounted smoke detector will be located in front of a fire wall Fire/Smoke damper in ceiling plenum. Told John to provide the information to the field inspector and provide on as-builts.
|
Issue and Print Permit | | | 9/8/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/6/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/6/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/6/2006 | | 9/6/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/6/2006 | | DONE |
|
|
|
spoke to lea@###-####/told permit was ready, permit#, project name & address, and fee
|
Alarm Plan Check | | | 8/31/2006 | | PASS |
|
|
|
Plans reviewed and approved by F. Varley without written comments.
|
Miscellaneous action | | | 8/22/2006 | | DONE |
|
|
|
Plan routed to FV for review.
|
Case Summary | | | 8/11/2006 | | DONE |
|
|
|
|
Application received | | | 8/11/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 8/11/2006 | | | | |
|
|
|
|