INSP-Final Inspection | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | DEFR |
Forrest France
|
|
|
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton
|
INSP-Final Inspection | 10/31/2008 | 11/4/2008 | 11/5/2008 | A | PART |
Forrest France
|
|
|
Remainder of notification devices including adjustments at the 2nd floor mechanical rooms passed field testing.
|
INSP-Alarm Testing | 10/27/2008 | 10/30/2008 | 10/30/2008 | A | PART |
Forrest France
|
|
|
Fire alarm notification devices tested okay at the 2nd floor mechanical room areas, common corridor, restrooms, locker room and mech. penthouse, EOL voltage is satisfactory,
|
INSP-Alarm Testing | 10/27/2008 | 10/29/2008 | 10/30/2008 | A | PART |
Forrest France
|
|
|
Testing for initiating devices at the cleanroom areas photo bays 8 and 9 including manual pull stations, heat detectors, UF smoke detectors, and door release completed satisfactory.
|
INSP-Alarm Testing | 10/20/2008 | 10/23/2008 | 10/23/2008 | A | CANC |
Forrest France
|
|
|
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
|
INSP-Alarm Testing | 10/20/2008 | 10/21/2008 | 10/21/2008 | A | PART |
Forrest France
|
|
|
Testing completed for 2nd floor mechanical area duct smoke detection devices, noted sample tube at one location missing end plug, three units not available for shutdown, also tested flow switch and two DD at the penthouse mechanical room. Additional SD at the 1st floor corridor tested okay.
|
INSP-Alarm Testing | 10/10/2008 | 10/16/2008 | 10/16/2008 | A | PART |
Forrest France
|
|
|
Tested smoke detectors at and above ceilings including door release and manual pull stations at the common corridors 1st and 2nd floors and electrical/mechanical areas on the 2nd floor. Noted overspaced smoke detection at the west 1st floor corridor and one incorrect address.
|
INSP-Alarm Testing | 10/3/2008 | 10/8/2008 | 10/8/2008 | A | PART |
Forrest France
|
|
|
Tested remainder of heat detection devices in building 2 at the non-clean common corridors and mechanical areas.
|
INSP-Alarm Testing | 9/26/2008 | 10/2/2008 | 10/2/2008 | A | DEFR |
Forrest France
|
|
|
Inspection request intended for permit FIR06-00620.
|
INSP-Alarm Testing | 4/23/2008 | 4/29/2008 | 4/29/2008 | A | PART |
Forrest France
|
|
|
Horn and strobe testing completed for the cleanroom areas only, noted locations on plan in need of revision.
|
INSP-Alarm Testing | 4/23/2008 | 4/28/2008 | 4/28/2008 | A | PART |
Forrest France
|
|
|
Completed preliminary walkthrough of cleanroom areas prior to fire alarm notification test to verify positioning, cd settings and spacing of horn/strobe appliances.
|
FIR-Aging Inspection | 3/14/2007 | 3/14/2007 | 3/16/2007 | | DONE |
Forrest France
|
|
|
work in progress
|
CHANGE STATUS TO (ISS) | | | 9/11/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/7/2006 | | PASS |
|
|
|
Approved per plan annotations at onsite visit.
|
Plan assigned to (Mary) | | | 8/18/2006 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 8/18/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|