INSP-Final Inspection | 8/28/2006 | 8/29/2006 | 8/29/2006 | P | PASS |
Troy Cobbley
|
|
|
Sprinkler piping is ok to cover. Two additional pendants have been provided to correct sprinkler spacing.
|
INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | FAIL |
Troy Cobbley
|
|
|
Pendant heads are exceeding 130 sq. ft. in the prep area, in front of the cooler and in the room that is accessible from the back of the building.
|
Plan assigned to (Bill) | 8/21/2006 | | 8/22/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | 8/21/2006 | | 8/22/2006 | | PASS |
|
|
|
Attached review comments to plans.
|