INSP-Final Inspection | 12/12/2006 | 12/12/2006 | 12/12/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground permit finaled
|
INSP-Final Inspection | 12/5/2006 | 12/6/2006 | 12/6/2006 | P | FAIL |
Troy Cobbley
|
|
|
Still need the alarm connections tested. Need two additional tamper switches for the anti-freeze loop backflow preventor per IFC 903.4.1, need forward flush, head wrench, backflow certification, trapeze calcs and wall to deck in the warehouse as per the previous inspection entry.
|
INSP-Sprinkler Rough-in/Hydro | 11/7/2006 | 11/8/2006 | 11/8/2006 | P | PART |
Forrest France
|
|
|
AG hydrostatic test of the wet and antifreeze systems are acceptable.
|
INSP-Sprinkler Rough-in | 10/19/2006 | 10/20/2006 | 10/20/2006 | P | PASS |
Troy Cobbley
|
|
|
Overhead sprinkler system rough-in is passed. Contractor needs to provide calculations for the trapeze hangers and provide a full height wall between the office area and the warehouse as shown on the plans.
|
INSP-Supply line flush | 10/17/2006 | 10/18/2006 | 10/18/2006 | A | PASS |
Troy Cobbley
|
|
|
Underground flush passed.
|
INSP-Supply line flush | 10/16/2006 | 10/17/2006 | 10/17/2006 | A | CANC |
Troy Cobbley
|
|
|
Contractor is not ready for the underground flush
|
INSP-Sprinkler Rough-in/Hydro | 10/16/2006 | 10/17/2006 | 10/17/2006 | A | PASS |
Troy Cobbley
|
|
|
Underground hydro test passed
|
Plan assigned to (Bill) | 8/22/2006 | | 10/4/2006 | | PASS |
|
|
|
10/4/2006 14:23:06 MWT - activity updated through activity FIRA22 from case FIR06-00750.
|
INSP-Sprinkler Rough-in | 8/25/2006 | 8/28/2006 | 8/28/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground piping is ok to bury.
|
Sprinkler Plan Check | 8/23/2006 | | 8/23/2006 | | PASS |
|
|
|
Passed subject to plan annotations.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/23/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/23/2006 | | DONE |
|
|
|
|
Telephone call | | | 8/23/2006 | | DONE |
|
|
|
spoke to randy@###-####/told permit was ready, permit#, project name & address, and fee
|
Inspection Record Card- Fire | 8/23/2006 | | 8/23/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/23/2006 | | |
|
|
|
|
Application received | | | 8/22/2006 | | |
|
|
|
|