Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR06-00644
StatusFinaled
Name GENERAL FIRE INC
Site Address 108 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/30/20071/30/20071/30/2007PPASS
DetailsForrest France
Hood permit finaled.
INSP-Alarm Testing1/30/20071/30/20071/30/2007PPASS
DetailsForrest France
Corrections verified, the hood suppression system operated correctly under test conditions.
INSP-Alarm Testing1/25/20071/26/20071/26/2007PCANC
DetailsForrest France
alex - after 2:30p; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall
INSP-Final Inspection1/10/20071/11/20071/11/2007PFAIL
DetailsForrest France
The hood suppression system failed to operate during testing, also advised contractor to call in related FA permit at at next inspection as both permits are issued to this same sub.
INSP-Alarm Testing12/11/200612/12/200612/12/2006PNR
DetailsForrest France
Pending a fire alarm permit for the interconnection of the hood suppression sytem to the existing building fire alarm system.
INSP-Final Inspection11/28/200611/28/200611/28/2006PFAIL
DetailsForrest France
The hood suppression system is required to be interconnected with the existing building fire alarm system, also need to provide separation method between the fryer and the adjacent griddle.
Application received  8/28/2006  
Issue and Print Permit  8/28/2006 DONE