INSP-Final Inspection | 1/30/2007 | 1/30/2007 | 1/30/2007 | P | PASS |
Forrest France
|
|
|
Hood permit finaled.
|
INSP-Alarm Testing | 1/30/2007 | 1/30/2007 | 1/30/2007 | P | PASS |
Forrest France
|
|
|
Corrections verified, the hood suppression system operated correctly under test conditions.
|
INSP-Alarm Testing | 1/25/2007 | 1/26/2007 | 1/26/2007 | P | CANC |
Forrest France
|
|
|
alex - after 2:30p; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall
|
INSP-Final Inspection | 1/10/2007 | 1/11/2007 | 1/11/2007 | P | FAIL |
Forrest France
|
|
|
The hood suppression system failed to operate during testing, also advised contractor to call in related FA permit at at next inspection as both permits are issued to this same sub.
|
INSP-Alarm Testing | 12/11/2006 | 12/12/2006 | 12/12/2006 | P | NR |
Forrest France
|
|
|
Pending a fire alarm permit for the interconnection of the hood suppression sytem to the existing building fire alarm system.
|
INSP-Final Inspection | 11/28/2006 | 11/28/2006 | 11/28/2006 | P | FAIL |
Forrest France
|
|
|
The hood suppression system is required to be interconnected with the existing building fire alarm system, also need to provide separation method between the fryer and the adjacent griddle.
|
Application received | | | 8/28/2006 | | |
|
|
|
|
Issue and Print Permit | | | 8/28/2006 | | DONE |
|
|
|
|