INSP-Final Inspection | 5/25/2007 | 5/29/2007 | 5/29/2007 | A | PASS |
Forrest France
|
|
|
Final fire alarm testing completed satisfactory, corrections repaired, permit finaled.
|
INSP-Final Inspection | 5/23/2007 | 5/25/2007 | 5/25/2007 | A | PART |
Forrest France
|
|
|
Verified required corrections, a/v notification tested acceptable, all dampers functioned properly except #77 which will need repair and retest, manual pulls and door release are satisfactory, smoke and heat detectors not tested at this time due to time constraints, will test remainder of alarm work at next scheduled inspection as discussed.
|
INSP-Final Inspection | 5/21/2007 | 5/23/2007 | 5/23/2007 | A | FAIL |
Forrest France
|
|
|
One a/v in the corridor is non-functional, dampers at two locations in the corridor did not close upon alarm condition, noted one relocated manual pull station is installed too high, one set of double doors is out of adjustment at the mag locks, fire dampers on zone 6 did not function upon smoke detection.
|
INSP-Final Inspection | 5/18/2007 | 5/21/2007 | 5/21/2007 | A | DEFR |
Forrest France
|
|
|
Inspection to be rescheduled.
|
INSP-Alarm Testing | 11/7/2006 | 11/8/2006 | 11/8/2006 | A | PART |
Forrest France
|
|
|
Fire alarm at the waiting area only per field inspection by M.Timmerman is acceptable, noted four damper locations with no access provided to visually confirm closure of the vanes.
|
INSP-Alarm Testing | 10/31/2006 | 11/1/2006 | 11/1/2006 | P | NR |
Forrest France
|
|
|
To be rescheduled per contractor as the project is not ready for inspection.
|
Issue and Print Permit | | | 9/22/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/13/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/13/2006 | | 9/13/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/13/2006 | | DONE |
|
|
|
spoke to jim@###-####/told permit was ready, project name, and fees
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/12/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/8/2006 | | PASS |
|
|
|
Approved by F. Varley "as noted" without written review comments.
|
Case Summary | | | 8/28/2006 | | DONE |
|
|
|
|
Application received | | | 8/28/2006 | | |
|
|
|
|
Inspection | 11/8/2006 | 11/8/2006 | | | PART |
|
|
|
Inspected fire alarm system operation in the new surgery waiting area of St Lukes Hospital. A/V syncronization and voice message Tested OK. EOL Voltage was 23.5VDC The smoke detectors and door hold release all tested OK. The in-duct smoke detector acces was OK and smoke detectors were operational, However, access doors on all 4 in-duct detectors do not provide visual access to the damper.
|
Plan assigned to (Mary) | 8/28/2006 | | | | |
|
|
|
|