| INSP-Final Inspection | 2/15/2007 | 2/15/2007 | 2/15/2007 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
| INSP-Alarm Testing | 2/13/2007 | 2/13/2007 | 2/13/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Items on from last inspection have been corrected.
|
| INSP-Alarm Testing | 2/6/2007 | 2/7/2007 | 2/8/2007 | P | FAIL |
Troy Cobbley
|
|
|
See Mike Timmermans entry from 2/7/2006
|
| INSP-Final Inspection | 1/24/2007 | 1/25/2007 | 1/26/2007 | P | FAIL |
Forrest France
|
|
|
Per field inspection completed by M. Timmerman defficiencies noted and some revisions will be required.
|
| INSP-Final Inspection | 1/22/2007 | 1/24/2007 | 1/24/2007 | P | DEFR |
Forrest France
|
|
|
Inspection rescheduled per conversation with contractor.
|
| Issue and Print Permit | | | 10/17/2006 | | DONE |
|
|
|
|
| Plan resubmittals received | | | 10/13/2006 | | |
|
|
|
|
| Alarm Plan Check | 10/13/2006 | | 10/13/2006 | | PASS |
|
|
|
Ready For Issue
|
| PLANS/APPL TAKEN TO FRONT DESK | | | 10/13/2006 | | |
|
|
|
Ready For Issue
|
| Inspection Record Card- Fire | 10/13/2006 | | 10/13/2006 | | DONE |
|
|
|
|
| Telephone call | | | 10/13/2006 | | DONE |
|
|
|
lft vm with dave whitting ###-#### that permit and fees are ready to be picked up
|
| Permit Ready to Issue | | | 10/13/2006 | | DONE |
|
|
|
|
| Plan assigned to (Mike) | 8/31/2006 | | 10/13/2006 | | PASS |
|
|
|
10/13/2006 13:57:36 MWT - activity updated through activity FIRA22 from case FIR06-00651.
|
| Telephone call | | | 10/12/2006 | | |
|
|
|
Faxed Fire Alarm Review to David Whitting at ADT. Copy of Plans Taken to Front Desk for Resubmittal Pickup.
|
| Telephone call | | | 10/12/2006 | | DONE |
|
|
|
resubmittal required no fee per Mike T.
|
| Plan resubmittals received | | | 10/9/2006 | | |
|
|
|
|
| Alarm Plan Check | 9/13/2006 | | 9/14/2006 | | FAIL |
|
|
|
Resubmittal Required see Fire Alarm Review Comments. Faxed Copy of Review to David Whitting ADT. Copy of submittal taken to front desk for return.
|
| Telephone call | | | 9/14/2006 | | DONE |
|
|
|
Faxed Fire Alarm Review to David Whiting ADT
|
| Application received | | | 8/29/2006 | | |
|
|
|
|
| Case Summary | | | 8/29/2006 | | DONE |
|
|
|
|
| Inspection | 2/7/2007 | 2/7/2007 | | | FAIL |
|
|
|
Fire Alarm System Inspection 2/7/2007 Conducted fire alarm inspection of devies noted and failed on 1/25/2007. All correction Items noted 1/25/2007 have been completed. However,
1.) The visual devices connected to the two new NAC power supplies are not in syncronization.
2.) No audible device installed in room 573 visiting area.
3.) Door release between corridor 7 and 8 doorr delay device is not working correctly smoke doors do not close.
4.) Audible levels in most areas of the building are very low and do not meet the audible level requirement for this facility.
5.) Battery current and EOL voltage Drops have not been checked
|
| Inspection | 1/25/2007 | 1/25/2007 | | | FAIL |
|
|
|
Fire Alarm System Inspection: 1/25/2007 Conducted fire alarm inspection at the Marquis Care Center to assist Forrest. The Fire Inspection failed due to the following defficiencies.
1. Smoke detectors 1-46 and 1-25 in west corridor outside the kitchen area did not operate or alarm.
2. Kitchen Hood manual release pull station handle broke durring the demonstration and inspection This was repaired before I left and is working OK now. All kitchen hood functions worked as required release Alarm Monitor, Fuel and Electric Shutoff and Pull Station in proper location. Hood Passed
3. Dining Room Horn Strobe Wrong cd. Corrected.
4. Sun Room Horn Strobe Wrong cd. Corrected
5. Lanudry room 355 smoke detectors not located as shown on approved plans.
6. House Keeping 748 has a 14" beam seperating the toom in half this is not shown on the submitted plans. Smoke detection is inadiquate for this room as currently designed. anorher smoke detector is required.
7. Horn Strobe in house keeping 748 has been changed to ceiling horn strobe. a wall seperates the room in half. The current A/V design is not adiquate for this room and must be redesigned.
8. Storage room 453 has a heat detector being used for door release. This detector was to be changed to a smoke detector per review.
9. Manual pull station in dayroom 569 not working.
10. Nurse station 570 horn strobe incorrect where it has been moved to. Must be increases to a minimum of 30 cd
11. Activity Room 573 East strobe incorrect 15/75, needs to be a minimum of 75 cd for this room.
12. Audible visual devices not checked for audibility or syncronization and must be checked. Battery sizes not checked. Panel verification and remote annunciators not checked.
Forrest contact me before you go to finish this inspection. I would be glad to help It may make things go faster Mike
|
| Alarm Plan Check | 10/12/2006 | | | | FAIL |
|
|
|
See Fire Alarm Review Comments
|