Information based on query as of Saturday, October 3, 2026.
Permit Information
Permit NumberFIR06-00651
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 909 E RESERVE ST
Project NameMARQUIS CARE - SHAW MOUNTAIN
Customer Number 
ePlanReview 
Description
The project includes the installation of New NAC Panel. New, Replacement and Relocation of Existing Audible / Visual devices scattered throughout the facility and Replacement of existing Duct Smoke Detectors to include new Remote LED Indicators and Test Switches. The project includes monitoring of the Existing Kitchen Hood Ansul System and the addition of one MPS, Area & Corridor smoke detectors that will be installed as indicated on the project plans. Building Permit BLD02-00194 and BLD05-00849 are not yet complete in this facility, Total area now indicated to be 43,366 sq. ft./ 423 occ. load/ V-1hour/ R-2 zone/ 40 psf . The building is fully sprinklered & alarmed and this remodel & code upgrade will create 2 builidngs of V-1 Hour with a 2-hour area separation wall dividing into areas of 20,747 sf East wing and a 22,619 sf West Wing. Maximum allowable area under 1997 UBC for each wing: Basic Area - 5,200 s.f. x 1.5 for two yards x 3 for fully sprinklered = 23,400 s.f.each side of 2-hour area separation wall. Existing C.O for 1972 edition, #1104 indicate 200 occupant load; D-3, V-1, 16,059 sq. ft., R-2 zone, 40 psf, C.U. 4-23-69. 1961 construction was for 30,820 s.f.; V-1hour; D3; FZ 3, Zone 'A'; OL - 176 + 47 office= 223 total
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/15/20072/15/20072/15/2007PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing2/13/20072/13/20072/13/2007PPASS
DetailsTroy Cobbley
Permit finaled. Items on from last inspection have been corrected.
INSP-Alarm Testing2/6/20072/7/20072/8/2007PFAIL
DetailsTroy Cobbley
See Mike Timmermans entry from 2/7/2006
INSP-Final Inspection1/24/20071/25/20071/26/2007PFAIL
DetailsForrest France
Per field inspection completed by M. Timmerman defficiencies noted and some revisions will be required.
INSP-Final Inspection1/22/20071/24/20071/24/2007PDEFR
DetailsForrest France
Inspection rescheduled per conversation with contractor.
Issue and Print Permit  10/17/2006 DONE
Plan resubmittals received  10/13/2006  
Alarm Plan Check10/13/2006 10/13/2006 PASS
Ready For Issue
PLANS/APPL TAKEN TO FRONT DESK  10/13/2006  
Ready For Issue
Inspection Record Card- Fire10/13/2006 10/13/2006 DONE
Telephone call  10/13/2006 DONE
lft vm with dave whitting ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  10/13/2006 DONE
Plan assigned to (Mike)8/31/2006 10/13/2006 PASS
10/13/2006 13:57:36 MWT - activity updated through activity FIRA22 from case FIR06-00651.
Telephone call  10/12/2006  
Faxed Fire Alarm Review to David Whitting at ADT. Copy of Plans Taken to Front Desk for Resubmittal Pickup.
Telephone call  10/12/2006 DONE
resubmittal required no fee per Mike T.
Plan resubmittals received  10/9/2006  
Alarm Plan Check9/13/2006 9/14/2006 FAIL
Resubmittal Required see Fire Alarm Review Comments. Faxed Copy of Review to David Whitting ADT. Copy of submittal taken to front desk for return.
Telephone call  9/14/2006 DONE
Faxed Fire Alarm Review to David Whiting ADT
Application received  8/29/2006  
Case Summary  8/29/2006 DONE
Inspection2/7/20072/7/2007  FAIL
Fire Alarm System Inspection 2/7/2007 Conducted fire alarm inspection of devies noted and failed on 1/25/2007. All correction Items noted 1/25/2007 have been completed. However,
1.) The visual devices connected to the two new NAC power supplies are not in syncronization.

2.) No audible device installed in room 573 visiting area.

3.) Door release between corridor 7 and 8 doorr delay device is not working correctly smoke doors do not close.

4.) Audible levels in most areas of the building are very low and do not meet the audible level requirement for this facility.

5.) Battery current and EOL voltage Drops have not been checked
Inspection1/25/20071/25/2007  FAIL
Fire Alarm System Inspection: 1/25/2007 Conducted fire alarm inspection at the Marquis Care Center to assist Forrest. The Fire Inspection failed due to the following defficiencies.

1. Smoke detectors 1-46 and 1-25 in west corridor outside the kitchen area did not operate or alarm.

2. Kitchen Hood manual release pull station handle broke durring the demonstration and inspection This was repaired before I left and is working OK now. All kitchen hood functions worked as required release Alarm Monitor, Fuel and Electric Shutoff and Pull Station in proper location. Hood Passed

3. Dining Room Horn Strobe Wrong cd. Corrected.

4. Sun Room Horn Strobe Wrong cd. Corrected

5. Lanudry room 355 smoke detectors not located as shown on approved plans.

6. House Keeping 748 has a 14" beam seperating the toom in half this is not shown on the submitted plans. Smoke detection is inadiquate for this room as currently designed. anorher smoke detector is required.

7. Horn Strobe in house keeping 748 has been changed to ceiling horn strobe. a wall seperates the room in half. The current A/V design is not adiquate for this room and must be redesigned.

8. Storage room 453 has a heat detector being used for door release. This detector was to be changed to a smoke detector per review.

9. Manual pull station in dayroom 569 not working.

10. Nurse station 570 horn strobe incorrect where it has been moved to. Must be increases to a minimum of 30 cd

11. Activity Room 573 East strobe incorrect 15/75, needs to be a minimum of 75 cd for this room.

12. Audible visual devices not checked for audibility or syncronization and must be checked. Battery sizes not checked. Panel verification and remote annunciators not checked.

Forrest contact me before you go to finish this inspection. I would be glad to help It may make things go faster Mike
Alarm Plan Check10/12/2006   FAIL
See Fire Alarm Review Comments