INSP-Final Inspection | 12/4/2006 | 12/5/2006 | 12/5/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Meeting | | | 11/3/2006 | | |
|
|
|
Had Meeting with Sam to discuss the syncronization issues with TI area and non TI area. We both agree if the syncronization can be completed that the location and mounting heights of the non TI area would not be required. Mike Timmerman & Sam Rogers
|
INSP-Final Inspection | 10/17/2006 | 10/23/2006 | 10/23/2006 | A | FAIL |
Forrest France
|
|
|
Manual pull stations at two locations within the area of work (NE and NW exits) are mounted too high, wall mounted notification devices at two hallways south of the TI area adjacent to open office areas are not in sync with the new ceiling AV's per contractor and are below min. height AFF. Provide approved plans on site at next inspection. Notified contractor to provide plans reflecting any changes on resubmittals or as-builts with inspectors approval.
|
Issue and Print Permit | | | 9/28/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/27/2006 | | |
|
|
|
Ready For Issue
|
Permit Ready to Issue | | | 9/27/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/27/2006 | | 9/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 9/27/2006 | | DONE |
|
|
|
spoke to charlie@###-####/told permit was ready, project name, and fee
|
Miscellaneous action | | | 9/22/2006 | | |
|
|
|
plans picked up, resubmittals required
|
Miscellaneous action | | | 9/15/2006 | | DONE |
|
|
|
Fax Copy of Review to Simplex Charlie Bayne 9-15-06
|
Telephone call | | | 9/15/2006 | | DONE |
|
|
|
spoke to charlie@###-####/told resubmittal was required and that these plans could be picked up
|
Application received | | | 9/5/2006 | | |
|
|
|
|
Plan assigned to (Mike) | 9/15/2006 | | | | |
|
|
|
|
Alarm Plan Check | 9/15/2006 | | | | FAIL |
|
|
|
Begin Fire Alarm Review
|
Alarm Plan Check | 9/27/2006 | | | | PASS |
|
|
|
Resubmittal Review
|