Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberFIR06-00671
StatusFinaled
Name GEM STATE FIRE PROTECTION
Site Address 3612 W OVERLAND RD
Project NameAMERICAN CLASSIFIED
Customer Number 
ePlanReview 
Description
American Classified - The fire sprinkler scope includes adding a new wet pipe system through out the new structure. All construction per the approved plans and attached comment list. This permit is attached to BLD05-02651.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/13/20073/15/20073/15/2007APASS
DetailsForrest France
Required corrections have been field verified for compliance, final fire sprinkler inspection passed, permit finaled.
INSP-Final Inspection3/7/20073/8/20073/8/2007AFAIL
DetailsForrest France
Ordinary temp SW heads in the skylights on the second floor are not permitted, need to provide a "911" sign at the outside bell, contractor to provide a pitot guage and playpipes to enable forward flow testing of the BFP as indicated in plan attatched fire code review notes.
Plan assigned to (Bill)11/20/2006 2/7/2007 PASS
2/7/2007 16:44:52 MWT - activity updated through activity FIRA22 from case FIR07-00104.
INSP-Sprinkler Rough-in/Hydro12/19/200612/20/200612/20/2006APART
DetailsForrest France
Overhead hydrostatic test passed. Noted two heads at the entryway high ceiling area which exceed max. allowable 130ft/2 for this system, the FDC ball drip will not function properly as installed, missing one flex coupling at the 21/2 feed to the lower office area where it passes through the floor, ssu's below the stairs at two locations are not installed, the remainder of system rough-in appears acceptable.
INSP-Sprinkler Rough-in12/14/200612/19/200612/19/2006PDEFR
DetailsForrest France
steve - 200 lb test ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith No time available to complete this inspection today, to be rescheduled per phone conversation with contractor as agreed.
INSP-Supply line flush12/14/200612/15/200612/15/2006APART
DetailsForrest France
UG fire supply line flush performed satisfactory.
INSP-Supply line flush12/13/200612/14/200612/14/2006ACANC
DetailsForrest France
Per phone call from contractor, not ready for inspection, to be rescheduled.
CHANGE STATUS TO (ISS)  12/5/2006 DONE
contractor picked up plans
(F) Reprint permit  12/5/2006 DONE
Issue and Print Permit  11/20/2006  
Inspection Record Card- Fire11/7/2006 11/7/2006 DONE
Permit Ready to Issue  11/7/2006 DONE
Sprinkler Plan Check  11/6/2006 PASS
Resubmitted revised plans, reviewed by B. Johnson.
PLANS/APPL TAKEN TO FRONT DESK  11/6/2006 DONE
Plan assigned to (Bill)9/6/2006 11/6/2006 PASS
11/6/2006 17:03:11 SLR - activity updated through activity FIRA22 from case FIR06-00671.
Plan resubmittals received  10/23/2006  
Plan re-subs submitted ///dld sent to fire
Sprinkler Plan Check  9/26/2006 FAIL
Plans reviewed by B. Johnson. Review faxed to Gem State.
Application received  9/6/2006