Permit Information
Permit NumberFIR06-00687
StatusFinaled
Name MICRON TECHNOLOGY INC
Site Address 8000 S FEDERAL WAY
Project Name 
Customer NumberC9867
ePlanReview 
Description
Fire Sprinkler System: C9867 SCOPE: RELOCATE WALL IN PROBE 1 BOOTIE ROOM AND PASS THRU

DEMO (D) 3 PENDANT SPRINKLER HEADS AND PIPING, INSTALL 5 NEW (N) PENDANT SPRINKLER HEADS AND PIPING FOR THE SMOCK (107A) AND BOOTIE (107B) ROOM REMODEL.

(NET WORK: INSTALL 2 NEW SPRINKLER HEADS)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20075/11/20075/11/2007APASS
DetailsForrest France
Fire sprinkler permit finaled.
Plan assigned to (SAM)12/8/2006 5/10/2007 PASS
5/10/2007 11:24:26 SLR - activity updated through activity FIRA22 from case FIR06-00687.
Sprinkler Plan Check5/10/2007 5/10/2007 PASS
The modified plans have been replaced with the originally approved plan set showing the sprihkler head in the pass through. Now ready for reinspectin on that basis.
PLANS/APPL TAKEN TO FRONT DESK  5/10/2007 DONE
Issue and Print Permit  5/10/2007 DONE
Sprinkler Plan Check12/21/2006 12/21/2006 FAIL
This is a Plan Modification to sheet FP2.1.1 REV1. dated 11/6/06, to delete a sprinkler in the pass through shown on the originally approved plans. No change from previous plan notes and discussion with Paul M. and Steve M indicating this sprinkler is required unless they can show a specific code allowance for removing it. No information has been provided. No further action taken at this visit.
Sprinkler Plan Check12/7/2006 12/7/2006 FAIL
Plans still out for review. No change made to add sprinkler back in the pass-through. Discussed with Paul. Requested their FPE provide us with the NFPA 13 or other applicable code references which he feels would justify this to be a non-sprinklered space within a required sprinklered building and we will consider it further. Otherwise, we will stay with the requirement for a sprinkler head within this space.
Plan resubmittals received  11/22/2006 DONE
Sprinkler Plan Check11/22/2006 11/22/2006 FAIL
A Plan modification was out for review showing the sprinkler in the pass-thru to be removed. Troy Cobbley refused to sign; referred to S. Rogers to evaluate. I looked at the situation this date and feel it should be sprinklered per req't of NFPA 13, 8.1.1 and because of potential for combustible material to be within the space; due to its size, it will accommodate large trash bins, combustible cartons and material, etc which are present in the areas on both sides of this pass through, and sprinklers are consistent with past practice at Micron.
INSP-Final Inspection11/6/200611/7/200611/13/2006APASS
DetailsForrest France
Fire sprinkler permit finaled.
Issue and Print Permit  9/27/2006 DONE
Sprinkler Plan Check  9/21/2006 PASS
Approved by TC 9/21/06; stamped and signed by SLR 9/21/06.
Plan assigned to (Bill)  9/13/2006 DONE
DetailsBill Alexander
This permit was created on the web by Paul Marcolina
Application received  9/13/2006 DONE
This permit was created on the web by Paul Marcolina