Permit Information
Permit NumberFIR06-00704
StatusFinaled
Name PROTEX
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG
Customer Number 
ePlanReview 
Description
This project is to install a new fire sprinkler monitoring system in the shell and core areas of a new office building. Work includes in-duct and HVAC duct smoke detection. Elevator lobby smoke detectors recall and shunt trip. Audible visual devices installed in the common and public areas. Una Mas Office Shell & Core Building - Is to construct a 50,280 square foot, three story office building with a 17,420 square foot basement and related site improvements. This building is constructed of a concrete basement, steel structural frame with steel stud exterior walls, metal deck and concrete floors and metal roof deck. The basement contains 27 parking spaces, 14 varying sized storage units, restrooms with showers conference room, mechanical room and circulation hallway. The first floor finished core area includes central corridor/lobby, restrooms, phone/data room. This is a shell and core permit only. Separate tenant improvement permits are required to finish this building for occupancy. This building is fully fire sprinklered. The sprinklers are used for one-hour fire-resistive substitution.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/1/20078/1/20078/1/2007PPASS
DetailsForrest France
Shell fire alarm work passed final inspection, permit finaled.
INSP-Final Inspection7/31/20077/31/20077/31/2007PPART
DetailsForrest France
Noted items at the previous inspection have been verified for completion, remainder of system testing passed, final pending clear panel-trouble due to a SD in the elevator shaft-need to repair or replace, will sign completion forms when panel is clear.
INSP-Final Inspection7/25/20077/26/20077/26/2007AFAIL
DetailsForrest France
Lacking notification coverage at the basement restrooms, low air switch is not adjusted properly, identify zone descriptors with central station, missing covers at two control modules, provide lock and label at the breaker to the FACP, provide as-built plans correctly reflecting field mods including deleted monitor points, need map at the panel, 2nd and 3rd floor ID's and elevator not tested at this time, SD at the 2nd floor lobby to be relocated to the drop ceiling.
INSP-Final Inspection7/23/20077/25/20077/25/2007ACANC
DetailsForrest France
No time available to complete inspection.
INSP-Final Inspection5/14/20075/16/20075/14/2007PCANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection2/27/20073/1/20073/1/2007PCANC
DetailsForrest France
Rafe''s phone. Phone #: ###-#### Inspection cancelled from web by: Terry Owsley
Issue and Print Permit  11/13/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  11/8/2006  
Ready For Issue
Inspection Record Card- Fire11/8/2006 11/8/2006 DONE
Telephone call  11/8/2006 DONE
t/c w Terry at Protex - ###-#### - permit ready - no fees
Permit Ready to Issue  11/8/2006 DONE
Plan assigned to (Mike)9/18/2006 11/7/2006 PASS
11/7/2006 16:01:37 SLR - activity updated through activity FIRA22 from case FIR06-00728.
Plan resubmittals received  11/1/2006  
Miscellaneous action  9/25/2006  
Faxed Fire Alarm Review to Applicant Rob Ahten and
System Designer DC Engineering. No Name on Application
Telephone call  9/25/2006 DONE
left vm@###-####/told permit requires resubmittal
Application received  9/18/2006  
Case Summary  9/18/2006 DONE
Alarm Plan Check9/25/2006   FAIL
Fire Alarm Review
Alarm Plan Check11/8/2006   PASS
Fire Alarm Resubmittal Review