INSP-Final Inspection | 12/11/2006 | 12/12/2006 | 12/12/2006 | P | PASS |
Forrest France
|
|
|
Items on previous c/n have been verified for completion, inspection passed.
|
INSP-Final Inspection | 11/27/2006 | 11/28/2006 | 11/28/2006 | A | FAIL |
Forrest France
|
|
|
Missing retaining straps at beam clamps, beam clamps are not approved to be attatched to pan decking, existing heads above the new drop ceiling shall be removed, one upright at the open area does not match the temp. rating of the adjacent heads, pendent in the break room is off axis.
|
Plan assigned to (Bill) | 9/20/2006 | | 11/9/2006 | | PASS |
|
|
|
11/9/2006 13:55:53 MWT - activity updated through activity FIRA22 from case FIR06-00851.
|
Issue permit | | | 10/4/2006 | | |
|
|
|
|
Inspection Record Card- Fire | 10/3/2006 | | 10/3/2006 | | DONE |
|
|
|
|
Telephone call | | | 10/3/2006 | | DONE |
|
|
|
tlk to lily that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/3/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/2/2006 | | DONE |
|
|
|
|
Sprinkler Plan Check | | | 9/27/2006 | | PASS |
|
|
|
Reviewed by B. Johnson.
|
Application received | | | 9/20/2006 | | |
|
|
|
|