INSP-Final Inspection | 7/31/2007 | 8/2/2007 | 8/2/2007 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed inspection, one strobe only device in a small room changed to a horn/strobe while on site due to inadequate dB levels, permit finaled.
|
FIR-Aging Inspection | 4/26/2007 | 4/26/2007 | 5/1/2007 | | DEFR |
Forrest France
|
|
|
|
Issue and Print Permit | | | 10/24/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/23/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/19/2006 | | DONE |
|
|
|
Revised plans approved without comments.
|
Alarm Plan Check | | | 10/12/2006 | | FAIL |
|
|
|
Inadequate strobe spacing; and need more details of curtains and ceiling heights to evaluate lack of strobe coverage within and beyond the curtained area.
|
Plan assigned to (Mary) | | | 10/3/2006 | | DONE |
Mary Froemke
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 10/3/2006 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|