INSP-Final Inspection | 4/13/2007 | 4/16/2007 | 4/16/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | FAIL |
Troy Cobbley
|
|
|
Project is not ready for a final inspection but the sprinkler piping is ok to cover. Per Jonathon the final will be called in when the alarm permit is ready.
|
INSP-Final Inspection | 3/26/2007 | 3/27/2007 | 3/27/2007 | A | FAIL |
Troy Cobbley
|
|
|
hanger did not get installed.
|
INSP-Final Inspection | 3/23/2007 | 3/23/2007 | 3/23/2007 | P | FAIL |
Troy Cobbley
|
|
|
I stopped the inspection after just looking at the east tenant. In the upstairs office areas there are two upright heads on the north side of the ducting that have not been installed, two uprights have been painted and one 2'-5" armover has no hanger
|
INSP-Sprinkler Rough-in/Hydro | 3/22/2007 | 3/22/2007 | 3/22/2007 | P | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed.
|
INSP-Sprinkler Rough-in/Hydro | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | FAIL |
Troy Cobbley
|
|
|
This is an overhead hydro which failed. The test was done twice today but did not hold pressure.
|
CHANGE STATUS TO (ISS) | | | 3/15/2007 | | DONE |
|
|
|
picked up plans and re-issued permit
|
(F) Reprint permit | | | 3/15/2007 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/15/2007 | | 3/15/2007 | | DONE |
|
|
|
|
Case Summary | | | 3/14/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/14/2007 | | DONE |
|
|
|
|
Telephone call | | | 3/14/2007 | | DONE |
|
|
|
tlk to lilly scales ###-#### that permit is ready to be picked up
|
Permit Ready to Issue | | | 3/14/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 2/27/2007 | | 3/12/2007 | | PASS |
|
|
|
As Built Plans & Calculation are approved by Bryan Johnson
|
INSP-Supply line flush | 3/2/2007 | 3/5/2007 | 3/5/2007 | P | PASS |
Troy Cobbley
|
|
|
The underground flush for the new building passed. The underground supply for the future building was not flushed.
|
INSP-Sprinkler Rough-in/Hydro | 3/2/2007 | 3/5/2007 | 3/5/2007 | P | PASS |
Troy Cobbley
|
|
|
The underground hydro for the new building passed but had to be measured for leakage. The underground supply for the future building was not tested.
|
INSP-Sprinkler Rough-in | 2/27/2007 | 2/27/2007 | 2/27/2007 | P | PASS |
Troy Cobbley
|
|
|
The 1" piping to the sidewall heads can be covered. Actual sizing will be verified when the requested resubmitted plans are on site for continuation of the inspection.
|
Plan resubmittals received | | | 2/27/2007 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 2/20/2007 | 2/20/2007 | 2/20/2007 | P | PASS |
Troy Cobbley
|
|
|
The underground piping is ok to cover. The sprinkler piping for the first floor offices is ok to cover as well. Per Nick Anderson the extended coverage sidewall heads will operate off of the existing pipe size but will still be resubmitted.
|
INSP-Sprinkler Rough-in | 2/15/2007 | 2/16/2007 | 2/16/2007 | A | FAIL |
Troy Cobbley
|
|
|
This inspection was for the office areas of the building only. The first problem is the CC upright heads are not installed correctly on the first floor. They exceed the listed 1 1/2" to 4" from the deck.The second problem is the floor plans for the second story area do not match what is existing. Pendants need to be installed in corridors and upright sprinkler heads are missing and additional uprights are going to be required at the office/warehouse separation wall. Thirdly the sprinkler protection for the interior of the outside canopy has been deleted and dry sidewall heads installed to provide protection below. The deleted portion of this sprinkler system was a remote area. Resubmittals, to the city of boise, will be required with all of the changes prior to inspection of the areas that have been effected.
|
INSP-Sprinkler Rough-in | 2/14/2007 | 2/15/2007 | 2/15/2007 | P | FAIL |
Troy Cobbley
|
|
|
Notified fire sprinkler contractor that the underground supply piping is required to be installed with the top of pipe below 4'-6" of the finish grade. A lively discussion ensued with the outcome being the piping is to be buried as stated, 4'-6".
|
Issue and Print Permit | | | 1/11/2007 | | DONE |
|
|
|
|
Sprinkler Plan Check | 1/5/2007 | | 1/10/2007 | | DONE |
|
|
|
Plan are approved as submitted by Bryan Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2007 | | |
|
|
|
|
Inspection Record Card- Fire | 1/10/2007 | | 1/10/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2007 | | DONE |
|
|
|
tlk to lily ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 1/10/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/19/2006 | | |
|
|
|
|