INSP-Final Inspection | 11/29/2006 | 11/29/2006 | 11/29/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 10/30/2006 | 10/30/2006 | 10/31/2006 | P | PART |
Forrest France
|
|
|
Fire alarm tested satisfactory, need to replace the damaged riser mounted flow switch as the housing base is cracked and the flex conduit and switch cover cannot be secured.
|
INSP-Final Inspection | 10/27/2006 | 10/27/2006 | 10/27/2006 | P | FAIL |
Forrest France
|
|
|
Outside bell failed to function, PIV valve locked shut.
|
INSP-Final Inspection | 10/26/2006 | 10/26/2006 | 10/27/2006 | P | DEFR |
Forrest France
|
|
|
Inspection rescheduled.
|
Issue and Print Permit | | | 10/18/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/17/2006 | | 10/17/2006 | | DONE |
|
|
|
|
Telephone call | | | 10/17/2006 | | DONE |
|
|
|
tlk to matt ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/17/2006 | | |
|
|
|
|
Plan assigned to (Mike) | 10/12/2006 | | 10/16/2006 | | PASS |
|
|
|
10/16/2006 14:38:09 MWT - activity updated through activity FIRA22 from case FIR06-00797.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/16/2006 | | |
|
|
|
Ready for Issue
|
Application received | | | 10/12/2006 | | |
|
|
|
|
Case Summary | | | 10/12/2006 | | |
|
|
|
|
Alarm Plan Check | 10/16/2006 | | | | PASS |
|
|
|
Fire Alarm Sprinkling System Review
|