INSP-Final Inspection | 1/26/2007 | 1/26/2007 | 1/30/2007 | P | PASS |
Troy Cobbley
|
|
|
This permit is finaled. One of the two duct smoke detectors has been deleted. Thet hvac unit has been removed from the roof top as requested..
|
INSP-Final Inspection | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | FAIL |
Troy Cobbley
|
|
|
One of the two duct detectors has been deleted. Per Mike Timmerman and I this detector needs to be installed as per the plans or the hvac unit needs to be removed. The one duct smoke detector that was installed has the sample tube installed backwards and pointing the wrong way. Also the donuts behind the detector are missing as well as the foam filters. I tested it anyway and it did shut the hvac unti down.
|
INSP-Final Inspection | 12/20/2006 | 12/27/2006 | 12/27/2006 | A | FAIL |
Forrest France
|
|
|
The two duct detectors are not installed correctly with respect to sample tube orientation and weatherproof enclosures. The panel, batteries, phone lines, SD, manual pull, and sprinkler monitoring all tested satisfactory.
|
INSP-Final Inspection | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | NR |
Forrest France
|
|
|
Per phone call from the contractor, the project is not ready for inspection due to HVAC equipment difficulties.
|
INSP-Final Inspection | 11/2/2006 | 11/2/2006 | 11/2/2006 | P | CANC |
Forrest France
|
|
|
No time available to complete this inspection request today, to be rescheduled per conversation with contractor.
|
Issue and Print Permit | | | 10/23/2006 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 10/18/2006 | | 10/20/2006 | | PASS |
|
|
|
10/20/2006 12:36:34 MWT - activity updated through activity FIRA22 from case FIR06-00810.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/20/2006 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 10/20/2006 | | 10/20/2006 | | DONE |
|
|
|
|
Telephone call | | | 10/20/2006 | | |
|
|
|
lft ms for bill herbert peak alarm ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/20/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/20/2006 | | |
|
|
|
|
Application received | | | 10/18/2006 | | |
|
|
|
|
Alarm Plan Check | 10/20/2006 | | | | PASS |
|
|
|
Sprinkler Fire Alarm System Review
|