Information based on query as of Thursday, September 10, 2026.
Permit Information
Permit NumberFIR06-00811
StatusFinaled
Name RFI
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
This is a new required fire alarm system in a new senior residential apartment complex and assisted living center. The fire alarm system includes common area and residential smoke detectors alarm notification interface with nurse call system fire smoke damper control. Sprinkler system and HVAC system monitoring, elevator recall and door hold open release. In-Duct smoke detectors are not installed in lieu of corridor smoke detection. This building is fully sprinklered for allowable area increase and requirements due to occupancy use group based on building stories & number of units. The Building permit Bld06-00579 is to construct a 57,480 sq. ft., three story, and 75 Unit (less than 800 sq. ft. per unit) assisted living community to include support facilities, for use by persons unable take action to provide self preservation in an emergency situation. This building is classified as Type IIA construction in accord with State of Idaho Facility Standards. Building elements listed in Table 601, 2003 IBC are to be non-combustible. A non-combustible framed 2-hour fire wall is to be constructed between the 'I2' occupancy and 'A2' occupancy. DRH05-00320 CUP05-00028 drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/19/2007 DONE
Sent an e-mail to Owner and Fire Alarm Vendor requesting the Submitted As-Built plans be corrected with a few devices that addresses are not shown Mike Timmerman 10-19-2007
INSP-Final Inspection10/1/200710/2/200710/2/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/28/20079/28/200710/1/2007PFAIL
DetailsTroy Cobbley
See Ken's field notes on the city approved plans for the items tested.
Alarm Plan Check  9/28/2007 PASS
Fire Alarm Review 3rd "Pass" with conditions on Review Notes.
PLANS/APPL TAKEN TO FRONT DESK  9/28/2007  
Ready for Issue - Conditions, see review comments
Inspection Record Card- Fire9/28/2007 9/28/2007 DONE
Telephone call  9/28/2007  
tlk to Roxanne ###-#### for Bob Beard that permit is ready to be picked up
Permit Ready to Issue  9/28/2007 DONE
Issue and Print Permit  9/28/2007 DONE
Miscellaneous action  9/25/2007  
Called the electrical contractor Dick Mather ###-####. They would like to have an inspection today, however, the resubmitted plans have not been issued yet. This is keeping the alarm contractor from being able to call in their inspections. We will be going to the site to continue the alarm testing of system devices that are ready for inspection. The electrical contractor told me that the problem with the in room detector sounder bases is still causing problems. They are still working on the problem. Entry made by Mike Timmerman
Alarm Plan Check  9/25/2007 FAIL
Fire Alarm Review 3rd
Miscellaneous action  9/25/2007  
Fax copy of review to applicant John Thompson RFI
Inspection  9/25/2007 PART
See documents for correction Items to be made.
INSP-Alarm Testing9/24/20079/24/20079/24/2007PFAIL
DetailsTroy Cobbley
The fire alarm panel, after testing between two to six room detectors will automatically silence the sounder bases. I do not know if the panel silences all building alarms. Also the data from one of the tenant rooms is being corrupted by the time it is received at the facp and is causing "wave form" errors at the facp. I spoke to the Pyrotronics technical support and they believe that the silencing problem could be a logic/programming issue. They need to view the program to tell. I stopped the inspection out of concerns that if it is a hardware issue all of the items tested would have to be retested when a new panel is installed. Just to make a note when the main fire alarm panel is reset it takes nearly 7 minutes to return to normal. It also takes around 15 seconds to activate the sounder bases in the rooms. I was told this is due to the size of the system and a slow processor in the fire alarm panel. I spoke to Sam Rogers about these concerns. This entry has been made under this permit only due to none access to the other permits because of their being in the "review status"
Plan resubmittals received  9/24/2007  
Received three copies of 1pg. voltage drop calcs, 1pg. battery calcs, and check for $330.00 (put in safe); taken to Mike Timmerman
Plan assigned to (Mike)9/19/2007 9/24/2007 PASS
9/24/2007 10:08:00 CMC - activity updated through activity FIRA22 from case FIR06-00957.
INSP-Alarm Testing9/18/20079/21/20079/21/2007ADONE
DetailsTroy Cobbley
See the city approved plans for locations tested by Ken.
INSP-Alarm Testing9/18/20079/20/20079/20/2007ACANC
DetailsTroy Cobbley
Overbooked with Micron plan review.
INSP-Alarm Testing9/18/20079/19/20079/19/2007ADONE
DetailsTroy Cobbley
Todays inspection was actually a conference with the fire alarm designer. Mike Timmerman and I went over the a/v and smoke detector deficiencies with him. Mike is allowing him to red line the resubmittals that are waiting in line at the city for review.
INSP-Alarm Testing9/17/20079/18/20079/18/2007ADONE
DetailsTroy Cobbley
No actual inspection was perform today do to multiple problems found.They include the fire alarm panel does not sound on second alarm. There are many over spaced detectors in lounge area. There are areas where smoke detectors and a/v's need to be added. In the dining areas the cieling mounts a/v'sare know mounted on the walls. The kithen area has same problems as well. The contractor needs to resubmit these changes.
INSP-Alarm Testing9/17/20079/17/20079/17/2007AFAIL
DetailsTroy Cobbley
The dialer was in trouble and would not clear. No test performed.
INSP-Alarm Testing9/13/20079/14/20079/14/2007ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested in area D.
INSP-Alarm Testing9/13/20079/13/20079/13/2007ACANC
DetailsTroy Cobbley
Overbooked
Miscellaneous action  9/5/2007  
The fire alarm vendor brought in a new set of fire alarm plans with plan modifications for review due to the increase in number of fire smoke dampers, fire sprinkler devices, addition of manual pull boxes due to IDHW requirements not IFC. The plans were not acceptable new devices were not shown connected to the initiating circuits, Visual notification in the HC rooms was not shown, Plans now use areas A.B,C,D instead of east, west, south and central wing. This needs to be revised on the resubmitted plans. We have asked the alarm vendor to correct the mistakes and omissions on the fire alarm plans, before we take them in. 9-5-07
INSP-Final Inspection8/31/20079/4/20079/4/2007ACANC
DetailsTroy Cobbley
No alarm inspection performed today. Just sprinklers were looked at.
CHANGE STATUS TO (ISS)  1/19/2007  
no fee due changed to issued status
PLANS/APPL TAKEN TO FRONT DESK  1/10/2007  
Ready for Issue
Inspection Record Card- Fire1/10/2007 1/10/2007 DONE
Telephone call  1/10/2007 DONE
t/c w roxanne at RFI -###-#### - permit ready and no fees
Permit Ready to Issue  1/10/2007 DONE
Plan assigned to (Mike)10/18/2006 1/10/2007 PASS
1/10/2007 12:21:58 MWT - activity updated through activity FIRA22 from case FIR06-00811.
Alarm Plan Check12/18/2006 1/10/2007 PASS
Waiting on generator Information, alarm vendor is using 4 hours of standby battery time and emergency generator backup. No Generator or fuel information was provided with the submittals.

Gernerator Information Received, Plans Issued.
Telephone call  12/27/2006  
Called fire alarm vendor again. Ryan Stills, Let him know we are still waiting on generator information to release fire alarm plans. (Voise Mail)
Telephone call  12/18/2006  
Called Ryan Stills with RFI the alarm vendor, told Ryan that I need information on the generator and fuel storage. Also if a contract for fuel delivery was in place.
Plan resubmittals received  12/11/2006  
Miscellaneous action  11/16/2006  
Faxed Copy of Failed Fire Alarm Review to RFI
Alarm Plan Check10/23/2006 10/24/2006 FAIL
Fire Alarm System Review I2 Area Bld06-00579. Fire alarm Plans submitted are not to scale. Required for review purposes.
Telephone call  10/23/2006  
Called Fire Alarm Applicant, Ryan Stills of RFI, in Beverton, Oregan. Left message with Ryan that the Fire Alarm Plan submitted is not to correct scale. Asked him to contact me at our office phone number. (Mike Timmerman)
Application received  10/18/2006  
Alarm Plan Check11/15/2006   FAIL
Fire Alarm Review Assisted Living East Wing