Information based on query as of Thursday, September 24, 2026.
Permit Information
Permit NumberFIR06-00812
StatusFinaled
Name RFI
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
This is a new required fire alarm system in a new senior residential apartment complex and assisted living center. The fire alarm system includes common area and residential smoke detectors alarm notification interface with nurse call system fire smoke damper control. Sprinkler system and HVAC system monitoring, elevator recall and door hold open release. In-Duct smoke detectors are not installed in lieu of corridor smoke detection. This building is fully sprinklered for allowable area increase and requirements due to occupancy use group based on building stories & number of units. To construct a 1-hour fire-resistive, wood & steel, three story, 62 unit (23 over 800 sq. ft.) residential retirement facility with a two story common assembly area with kitchen. All fire resistive construction per listed assemblies on plans. There is a 1-hour fire barrier wall between the R2/A2 areas for fire area compliance. DRH05-00320 CUP05-00028 drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/19/2007 PEND
Sent an e-mail to Owner and Fire Alarm Vendor requesting the Submitted As-Built plans be correcte with a few devices that addresses are not shown Mike Timmerman 10-19-2007
INSP-Final Inspection10/1/200710/2/200710/2/2007APASS
DetailsTroy Cobbley
permit finaled.
INSP-Final Inspection9/28/200710/1/200710/1/2007AFAIL
DetailsTroy Cobbley
See Ken's notes on the city approved plans for items tested and deficiencies found.
Alarm Plan Check  9/28/2007 PASS
Fire Alarm Review 3rd "Pass" with conditions
PLANS/APPL TAKEN TO FRONT DESK  9/28/2007  
Ready for Issue With Conditions See Review Comments
Inspection Record Card- Fire9/28/2007 9/28/2007 DONE
Telephone call  9/28/2007 DONE
tlk to Roxanne ###-#### for Bob Beard that permit is ready to be picked up
Permit Ready to Issue  9/28/2007 DONE
Issue and Print Permit  9/28/2007 DONE
Alarm Plan Check  9/25/2007 FAIL
Fire Alarm Review 3rd
Miscellaneous action  9/25/2007  
Fax copy of review to Alarm Vendor John Thompson RFI
Plan assigned to (Mike)9/19/2007 9/24/2007 PASS
9/24/2007 09:25:51 CMC - activity updated through activity FIRA22 from case FIR06-00958.
Plan resubmittals received  9/24/2007  
Received three copies of 1pg. voltage drop calcs, 1pg. battery calcs, and check for $330.00 (put in safe); taken to Mike Timmerman
Miscellaneous action  9/5/2007  
The fire alarm vendor brought in a new set of fire alarm plans with plan modifications for review due to the increase in number of fire smoke dampers, fire sprinkler devices, addition of manual pull boxes due to IDHW requirements not IFC. The plans were not acceptable new devices were not shown connected to the initiating circuits, Visual notification in the HC rooms was not shown, Plans now use areas A.B,C,D instead of east, west, south and central wing. This needs to be revised on the resubmitted plans. We have asked the alarm vendor to correct the mistakes and omissions on the fire alarm plans, before we take them in. 9-5-07
INSP-Final Inspection8/31/20079/4/20079/4/2007ACANC
DetailsTroy Cobbley
No alarm inspection performed today. Just sprinklers were looked at.
Telephone call  8/22/2007  
Received call from fire alarm vendor John Thompson RFI ###-####. He asked if a resubmittal would be required due to all the changes on the project. I asked him to check with Troy and use a rule of thumb of over 4 minor changes usually yes but best to check with the field inspector.
CHANGE STATUS TO (ISS)  1/19/2007  
changed status to issued. no fee due
PLANS/APPL TAKEN TO FRONT DESK  1/10/2007  
Ready for Issue
Inspection Record Card- Fire1/10/2007 1/10/2007 DONE
Telephone call  1/10/2007 DONE
t/c w roxanne at RFI -###-#### - permit ready and no fees
Permit Ready to Issue  1/10/2007 DONE
Plan assigned to (Mike)10/18/2006 1/10/2007 PASS
1/10/2007 12:32:29 MWT - activity updated through activity FIRA22 from case FIR06-00812.
Alarm Plan Check  1/10/2007 PASS
Waiting on generator Information, alarm vendor is using 4 hours of standby battery time and emergency generator backup. No Generator or fuel information was provided with the submittals.

Generator Information Received, Plans Issued 01/10/2007
Telephone call  12/18/2006  
Called Ryan Stills with RFI the alarm vendor, told Ryan that I need information on the generator and fuel storage. Also if a contract for fuel delivery was in place.
Plan resubmittals received  12/11/2006  
Alarm Plan Check  11/16/2006 FAIL
Fire Alarm System Review Center and South Wing
Miscellaneous action  11/16/2006  
Faxed Copy of Failed Fire Alarm Review to RFI
Alarm Plan Check  10/23/2006 FAIL
Fire Alarm System Plan Review Plans not to Scale
Telephone call  10/23/2006  
Called Fire Alarm Applicant, Ryan Stills of RFI, in Beverton, Oregan. Left message with Ryan that the Fire Alarm Plan submitted is not to correct scale. Asked him to contact me at our office phone number. (Mike Timmerman)
Application received  10/18/2006