Information based on query as of Thursday, September 17, 2026.
Permit Information
Permit NumberFIR06-00813
StatusFinaled
Name RFI
Site Address 5850 N FIVE MILE RD
Project NameBONAVENTURE PLACE
Customer Number 
ePlanReview 
Description
This is a new required fire alarm system in a new senior residential apartment complex and assisted living center. The fire alarm system includes common area and residential smoke detectors alarm notification interface with nurse call system fire smoke damper control. Sprinkler system and HVAC system monitoring, elevator recall and door hold open release. In-Duct smoke detectors are not installed in lieu of corridor smoke detection. This building is fully sprinklered for allowable area increase & compliance with occupancy use group. To construct a 1-hour fire-resistive, three story, 69 unit (26 units > 800 sq. ft.), multi family residential facility, separated from adjacent 'A2' Dining/common use area by a 2-hour fire wall to allow review of this portion as a stand alone structure for area & construction type. All fire-resistive assemblies shall be as called out on plans. DRH05-00320 CUP05-00028 drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/19/2007 PEND
Sent an e-mail to Owner and Fire Alarm Vendor requesting the Submitted As-Built plans be correcte with a few devices that addresses are not shown Mike Timmerman 10-19-2007
INSP-Final Inspection10/1/200710/2/200710/2/2007APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection9/28/200710/1/200710/1/2007AFAIL
DetailsTroy Cobbley
See Ken's notes on the city approved plans for items tested and deficiencies found.
Alarm Plan Check  9/28/2007 PASS
Fire Alarm Review 3rd "Pass" With Conditions See Review Comments
PLANS/APPL TAKEN TO FRONT DESK  9/28/2007  
Ready for Issue With Conditions See Review Comments
Inspection Record Card- Fire9/28/2007 9/28/2007 DONE
Telephone call  9/28/2007 DONE
tlk to Roxanne ###-#### for Bob Beard that permit is ready to be picked up
Permit Ready to Issue  9/28/2007 DONE
Issue and Print Permit  9/28/2007 DONE
Alarm Plan Check  9/25/2007 FAIL
Fire Alarm Review 3rd
Miscellaneous action  9/25/2007  
Fax copy of the Review to Alarm Vendor John Thompson RFI
Plan assigned to (Mike)9/19/2007 9/24/2007 PASS
9/24/2007 10:09:59 CMC - activity updated through activity FIRA22 from case FIR06-00956.
Plan resubmittals received  9/24/2007  
Received three copies of 1pg. voltage drop calcs, 1pg. battery calcs, and check for $330.00 (put in safe); taken to Mike Timmerman
INSP-Alarm Testing9/12/20079/12/20079/13/2007PDONE
DetailsTroy Cobbley
The fire alarm panel manufacturer, phone lines and supervision of NAC 4 and NAC 5 were verified. The smoke detector in the facp room and down the corridor as marked on the plans were tested. I found that the smoke detector and audio/visual were both overspaced from the end of the corridor. Also a NAC panel has been added in the facp room. Plans need to be resubmitted showing the new NAC. The facp was in trouble due to missing monitor modules at the roof top units. I went over requirements with the owner, building contractor, electrical contractor and fire alarm contractor.
Plan resubmittals received  9/10/2007  
received app. (5) pages & letter of transmittal & "3" sets of plans including D, FA-1, FA-2, FA-3, FA-4, FA-5, FA-6, FA-7, FA-8, FA-9, FA-10, FA-11, FA-12, FA-13, FA-14, FA-15, FA-16, & FA-17--plans taken to Mike Timmerman
Miscellaneous action  9/5/2007  
The fire alarm vendor brought in a new set of fire alarm plans with plan modifications for review due to the increase in number of fire smoke dampers, fire sprinkler devices, addition of manual pull boxes due to IDHW requirements not IFC. The plans were not acceptable new devices were not shown connected to the initiating circuits, Visual notification in the HC rooms was not shown, Plans now use areas A.B,C,D instead of east, west, south and central wing. This needs to be revised on the resubmitted plans. We have asked the alarm vendor to correct the mistakes and omissions on the fire alarm plans, before we take them in. 9-5-07
INSP-Final Inspection8/31/20079/4/20079/4/2007ACANC
DetailsTroy Cobbley
No alarm inspection performed today. Just sprinklers were looked at.
INSP-Conference8/29/20078/31/20078/31/2007ADONE
DetailsTroy Cobbley
The fire alarm contractor wanted to know the specifics of why I can't dedicate specific times to show up and spend doing their inspection.
CHANGE STATUS TO (ISS)  1/19/2007  
no fee due. changed status is issued
PLANS/APPL TAKEN TO FRONT DESK  1/10/2007  
Ready for Issue
Inspection Record Card- Fire1/10/2007 1/10/2007 DONE
Telephone call  1/10/2007 DONE
t/c w roxanne at RFI -###-#### - permit ready and no fees
Permit Ready to Issue  1/10/2007 DONE
Plan assigned to (Mike)10/18/2006 1/10/2007 PASS
1/10/2007 12:33:54 MWT - activity updated through activity FIRA22 from case FIR06-00813.
Alarm Plan Check12/13/2006 1/10/2007 PASS
Waiting on generator Information, alarm vendor is using 4 hours of standby battery time and emergency generator backup. No Generator or fuel information was provided with the submittals.

Generator Information Received, Plans Issued 01/10/2007
Telephone call  12/18/2006  
Called Ryan Stills with RFI the alarm vendor, told Ryan that I need information on the generator and fuel storage. Also if a contract for fuel delivery was in place.
Plan resubmittals received  12/11/2006  
Miscellaneous action  11/16/2006  
Faxed Failed Rire Alarm Review to RFI
Telephone call  10/23/2006  
Called Fire Alarm Applicant, Ryan Stills of RFI, in Beverton, Oregan. Left message with Ryan that the Fire Alarm Plan submitted is not to correct scale. Asked him to contact me at our office phone number. (Mike Timmerman)
Application received  10/18/2006  
Alarm Plan Check10/23/2006   FAIL
Fire Alarm System Review
Alarm Plan Check11/16/2006   FAIL
Fire Alarm System Review