Miscellaneous action | | | 10/19/2007 | | PEND |
|
|
|
Sent an e-mail to Owner and Fire Alarm Vendor requesting the Submitted As-Built plans be correcte with a few devices that addresses are not shown Mike Timmerman 10-19-2007
|
INSP-Final Inspection | 10/1/2007 | 10/2/2007 | 10/2/2007 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 9/28/2007 | 10/1/2007 | 10/1/2007 | A | FAIL |
Troy Cobbley
|
|
|
See Ken's notes on the city approved plans for items tested and deficiencies found.
|
Alarm Plan Check | | | 9/28/2007 | | PASS |
|
|
|
Fire Alarm Review 3rd "Pass" With Conditions See Review Comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/28/2007 | | |
|
|
|
Ready for Issue With Conditions See Review Comments
|
Inspection Record Card- Fire | 9/28/2007 | | 9/28/2007 | | DONE |
|
|
|
|
Telephone call | | | 9/28/2007 | | DONE |
|
|
|
tlk to Roxanne ###-#### for Bob Beard that permit is ready to be picked up
|
Permit Ready to Issue | | | 9/28/2007 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/28/2007 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/25/2007 | | FAIL |
|
|
|
Fire Alarm Review 3rd
|
Miscellaneous action | | | 9/25/2007 | | |
|
|
|
Fax copy of the Review to Alarm Vendor John Thompson RFI
|
Plan assigned to (Mike) | 9/19/2007 | | 9/24/2007 | | PASS |
|
|
|
9/24/2007 10:09:59 CMC - activity updated through activity FIRA22 from case FIR06-00956.
|
Plan resubmittals received | | | 9/24/2007 | | |
|
|
|
Received three copies of 1pg. voltage drop calcs, 1pg. battery calcs, and check for $330.00 (put in safe); taken to Mike Timmerman
|
INSP-Alarm Testing | 9/12/2007 | 9/12/2007 | 9/13/2007 | P | DONE |
Troy Cobbley
|
|
|
The fire alarm panel manufacturer, phone lines and supervision of NAC 4 and NAC 5 were verified. The smoke detector in the facp room and down the corridor as marked on the plans were tested. I found that the smoke detector and audio/visual were both overspaced from the end of the corridor. Also a NAC panel has been added in the facp room. Plans need to be resubmitted showing the new NAC. The facp was in trouble due to missing monitor modules at the roof top units. I went over requirements with the owner, building contractor, electrical contractor and fire alarm contractor.
|
Plan resubmittals received | | | 9/10/2007 | | |
|
|
|
received app. (5) pages & letter of transmittal & "3" sets of plans including D, FA-1, FA-2, FA-3, FA-4, FA-5, FA-6, FA-7, FA-8, FA-9, FA-10, FA-11, FA-12, FA-13, FA-14, FA-15, FA-16, & FA-17--plans taken to Mike Timmerman
|
Miscellaneous action | | | 9/5/2007 | | |
|
|
|
The fire alarm vendor brought in a new set of fire alarm plans with plan modifications for review due to the increase in number of fire smoke dampers, fire sprinkler devices, addition of manual pull boxes due to IDHW requirements not IFC. The plans were not acceptable new devices were not shown connected to the initiating circuits, Visual notification in the HC rooms was not shown, Plans now use areas A.B,C,D instead of east, west, south and central wing. This needs to be revised on the resubmitted plans. We have asked the alarm vendor to correct the mistakes and omissions on the fire alarm plans, before we take them in. 9-5-07
|
INSP-Final Inspection | 8/31/2007 | 9/4/2007 | 9/4/2007 | A | CANC |
Troy Cobbley
|
|
|
No alarm inspection performed today. Just sprinklers were looked at.
|
INSP-Conference | 8/29/2007 | 8/31/2007 | 8/31/2007 | A | DONE |
Troy Cobbley
|
|
|
The fire alarm contractor wanted to know the specifics of why I can't dedicate specific times to show up and spend doing their inspection.
|
CHANGE STATUS TO (ISS) | | | 1/19/2007 | | |
|
|
|
no fee due. changed status is issued
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2007 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 1/10/2007 | | 1/10/2007 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2007 | | DONE |
|
|
|
t/c w roxanne at RFI -###-#### - permit ready and no fees
|
Permit Ready to Issue | | | 1/10/2007 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 10/18/2006 | | 1/10/2007 | | PASS |
|
|
|
1/10/2007 12:33:54 MWT - activity updated through activity FIRA22 from case FIR06-00813.
|
Alarm Plan Check | 12/13/2006 | | 1/10/2007 | | PASS |
|
|
|
Waiting on generator Information, alarm vendor is using 4 hours of standby battery time and emergency generator backup. No Generator or fuel information was provided with the submittals.
Generator Information Received, Plans Issued 01/10/2007
|
Telephone call | | | 12/18/2006 | | |
|
|
|
Called Ryan Stills with RFI the alarm vendor, told Ryan that I need information on the generator and fuel storage. Also if a contract for fuel delivery was in place.
|
Plan resubmittals received | | | 12/11/2006 | | |
|
|
|
|
Miscellaneous action | | | 11/16/2006 | | |
|
|
|
Faxed Failed Rire Alarm Review to RFI
|
Telephone call | | | 10/23/2006 | | |
|
|
|
Called Fire Alarm Applicant, Ryan Stills of RFI, in Beverton, Oregan. Left message with Ryan that the Fire Alarm Plan submitted is not to correct scale. Asked him to contact me at our office phone number. (Mike Timmerman)
|
Application received | | | 10/18/2006 | | |
|
|
|
|
Alarm Plan Check | 10/23/2006 | | | | FAIL |
|
|
|
Fire Alarm System Review
|
Alarm Plan Check | 11/16/2006 | | | | FAIL |
|
|
|
Fire Alarm System Review
|