INSP-Final Inspection | 4/4/2007 | 4/5/2007 | 4/5/2007 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. One sample tube was pointed the wrong way and was corrected during the inspection. Also noted that one duct detector housing was coming lose from the duct. This was also corrected during the inspection.
|
INSP-Final Inspection | 4/2/2007 | 4/3/2007 | 4/3/2007 | P | FAIL |
Troy Cobbley
|
|
|
Sample tubes are mounted backwards. No test performed.
|
FIR-Aging Inspection | 1/31/2007 | 1/31/2007 | 2/6/2007 | | NR |
Troy Cobbley
|
|
|
work is in progress
|
Plan assigned to (Mike) | 10/20/2006 | | 10/27/2006 | | PASS |
|
|
|
10/27/2006 12:11:09 MWT - activity updated through activity FIRA22 from case FIR06-00821.
|
Alarm Plan Check | 10/26/2006 | | 10/27/2006 | | PASS |
|
|
|
Begin Fire Alarm Review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/27/2006 | | |
|
|
|
Ready For Issue
|
Inspection Record Card- Fire | 10/27/2006 | | 10/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 10/27/2006 | | DONE |
|
|
|
tlk to charlie ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 10/27/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 10/26/2006 | | |
|
|
|
Contacted Mechanical Engineer Don Poplin at LAW/KINGDON INC. ###-####. Questioned Don about fire smoke dampers installed in floor for AHU #1 AHU#2 and AHU#3. Don will be faxing over an ammendment to the plans indicating that these dampers are to close only when the AHU(s) for Tenant Zone #1 or Tenant Zone #5 required to close for smoke control and tied into the Mall smoke control system.
|
Application received | | | 10/20/2006 | | |
|
|
|
|