Permit Information
Permit NumberFIR06-00835
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 330 N MILWAUKEE ST
Project NameTHE CHEESECAKE FACTORY BTS
Customer Number 
ePlanReview 
Description
install fire system for main hood system, and fire system for back hood system for Cheesecake Factory (2 systems total)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/21/200611/22/200611/22/2006APASS
DetailsTroy Cobbley
Hood suppression system operated correctly
INSP-Final Inspection11/20/200611/21/200611/21/2006AFAIL
DetailsTroy Cobbley
The lightes under the west hood in the back kitchen area did not turn off when the hood was activated. Signage at the pull stations is still needed.
INSP-Final Inspection11/17/200611/20/200611/20/2006PFAIL
DetailsTroy Cobbley
Did not test the systems because not all of the lights were operating on the main hood so I could not verify electrical shutoff. Also both fryers do not meet the 4' rule of outer lip of hood to the cooking surface as stated in the IMC. Also need signs for the manual pull stations.
Application received  10/26/2006  
Issue and Print Permit  10/26/2006 DONE