Permit Information
Permit NumberFIR06-00842
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 307 S ROOSEVELT ST
Project NameSenior Housing Apartments "B"
Customer Number 
ePlanReview 
Description
To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated, in a new 4,655-ft/2 two story apartment building. Contract is starting at the discharge side of a 2" Wilkins Series 950XL Backflow Double Check control. An NFPA 13R fire sprinkler protection system is required through out the living area and the exterior entry ways. System shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes single underground water supply, the system backflow prevention device and domestic shut off valve (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-00994.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/7/20073/7/20073/7/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in/Hydro2/27/20072/27/20072/27/2007APASS
DetailsTroy Cobbley
Overhead hydro test passed.
INSP-Supply line flush1/8/20071/8/20071/8/2007PPASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in/Hydro12/21/200612/22/200612/22/2006APASS
DetailsTroy Cobbley
Sprinkler piping is ok to cover. Tenting inspection passed.
INSP-Sprinkler Rough-in/Hydro12/19/200612/19/200612/19/2006PPASS
DetailsTroy Cobbley
Sprinkler rough-in passed. Piping connecting the first and second floors has not been installed yet. No tenting has been done yet either.
Sprinkler Plan Check  11/15/2006 PASS
Reviewed by B. Johnson. Approved with conditions subject to field verification.
PLANS/APPL TAKEN TO FRONT DESK  11/15/2006 DONE
Inspection Record Card- Fire11/15/2006 11/15/2006 DONE
Telephone call  11/15/2006 DONE
lft vm with tom dutkus ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  11/15/2006  
Issue and Print Permit  11/15/2006 DONE
Application received  10/27/2006  
Pending Assignment by SAM10/27/2006