Permit NumberFIR06-00874
StatusFinaled
Name WESTERN STATES FIRE PROTECTION
Site Address 9288 W EMERALD ST
Project Name 
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:
(T-MOBILE COMMUNICATIONS) This building is fire sprinklered for area increase. To construct a 9,307 square foot telephone exchange tenant space within an existing 20,634 square foot building. A new double-interlock pre-action valve will control the sprinkler with in a new Switch Gear room. The Switch Gear Room will be protected above and below the ceiling. The existing 2.5" main will serve as the supply to the new auxiliary riser. Sections of the existing piping will be relocated to accommodate the construction. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/22/20073/22/20073/23/2007PPASS
DetailsTroy Cobbley
permit finaled
CHANGE STATUS TO (ISS)  3/22/2007 DONE
troy picked up the permit and took to rick at western states 3/19/2007
INSP-Final Inspection3/19/20073/19/20073/19/2007PPART
DetailsTroy Cobbley
Hydro test for the pre-action system passed. Hangers have been attached to the bottom chord of the trusses. An engineer needs to sign off on this or the hanger need to go to the top chord.
Sprinkler Plan Check3/16/2007 3/19/2007 PASS
As-built resubmittal plans reviewed and approved by B. Johnson. Additional fee applies due to increased number of sprinkler heads.
PLANS/APPL TAKEN TO FRONT DESK  3/19/2007 DONE
Permit Ready to Issue  3/19/2007  
Inspection Record Card- Fire3/19/2007 3/19/2007 DONE
Plan resubmittals received  3/16/2007  
Received letter of transmittal, application, 1pg. of e-mails between Bryan Johnson and Robert Escue, copy of fire sprinkler permit, TI Remodel Cover Sheet, Fire Sprinkler Hydraulic Calcs and cover sheet (3 copies), and 3 copies of page FP-1 with product description; routed to fire plan review
Telephone call  3/14/2007 DONE
telcon with spk contractor re procedures for resubmitting as-builts and calc's. Okay to not resubmit data sheets that have not changed; will resubmit three sets of plans & new calc's for new design area.
INSP-Sprinkler Rough-in/Hydro3/12/20073/12/20073/12/2007ACANC
DetailsTroy Cobbley
To be rescheduled per Rick
INSP-Sprinkler Rough-in/Hydro3/8/20073/8/20073/9/2007PFAIL
DetailsTroy Cobbley
Hydro test for the pre-action room failed
INSP-Sprinkler Rough-in/Hydro3/1/20073/2/20073/2/2007AFAIL
DetailsTroy Cobbley
Above ground hydro test failed.
INSP-Sprinkler Rough-in2/6/20072/6/20072/6/2007PFAIL
DetailsTroy Cobbley
Inspection was for just the office areas not the pre-action area. The office areas can not be covered yet due to insulation falling from the deck and creating obstructions to the upright sprinkler heads. Also an upright needs to be added in the west restroom due to an overspacing issue. The plans need to be resubmitted to the city for approval due to the amount of additional upright heads on the pre-action system. Many of these heads are in the hydraulic remote area.
INSP-Conference12/28/200612/29/200612/29/2006ADONE
DetailsTroy Cobbley
Contractor will have to attach earthquake bracing to the top of the trusses, they will have to resubmit if the change the supply to the preaction system and the duct can not be treated as obstructed construction. No approved plans were on site for review.
Issue and Print Permit  11/29/2006 DONE
Sprinkler Plan Check  11/28/2006 PASS
Reviewed by B. Johnson.
PLANS/APPL TAKEN TO FRONT DESK  11/28/2006 DONE
Inspection Record Card- Fire11/28/2006 11/28/2006 DONE
Telephone call  11/28/2006 DONE
tlk to robert escue ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  11/28/2006  
Application received  11/9/2006  
Pending Assignment by SAM11/9/2006    
Pending Assignment by SAM3/16/2007