INSP-Final Inspection | 12/27/2006 | 12/28/2006 | 12/28/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Alarm Plan Check | 12/27/2006 | | 12/27/2006 | | PASS |
|
|
|
Fire Alarm Plan Modification
|
Telephone call | | | 12/27/2006 | | DONE |
|
|
|
t/c w todd selman ###-#### - permit ready and fees given ($110.25 - for the 5th review)
|
Miscellaneous action | | | 12/27/2006 | | DONE |
|
|
|
picked up plans and paid one of the resubmittal fees (110.25)
|
(F) Reprint permit | | | 12/27/2006 | | DONE |
|
|
|
|
INSP-Final Inspection | 12/19/2006 | 12/20/2006 | 12/21/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need to provide an a/v in the breakroom, attach wire to structure and resubmit drawings showing wall changes and device relocations.
|
Plan resubmittals received | | | 12/21/2006 | | |
|
|
|
|
Plan assigned to (Mike) | 11/13/2006 | | 12/19/2006 | | PASS |
|
|
|
12/19/2006 09:43:55 MWT - activity updated through activity FIRA22 from case FIR06-00878.
|
Alarm Plan Check | 12/19/2006 | | 12/19/2006 | | PASS |
|
|
|
Fire alarm review 4th review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/19/2006 | | |
|
|
|
Ready for Issue
|
Inspection Record Card- Fire | 12/19/2006 | | 12/19/2006 | | DONE |
|
|
|
|
Telephone call | | | 12/19/2006 | | DONE |
|
|
|
t/c w Keith Olstrom at Vanguard ###-#### - permit ready and fees given ($374.70)
|
Permit Ready to Issue | | | 12/19/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/19/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/18/2006 | | |
|
|
|
|
Plan resubmittals received | | | 12/15/2006 | | |
|
|
|
|
Alarm Plan Check | 12/13/2006 | | 12/13/2006 | | FAIL |
|
|
|
Fire Alarm Review 3rd Time, No Floor Plan Included
|
Miscellaneous action | | | 12/13/2006 | | |
|
|
|
Faxed copy of the fire alarm review to alarm vendor Vanguard Protection. Keith Olstrom
|
Telephone call | | | 12/13/2006 | | DONE |
|
|
|
t/c w Keith Olstrom at Vanguard Protection - ###-#### - permit needs to be picked up and re-submitted
|
Issue permit | | | 12/13/2006 | | |
|
|
|
|
Plan resubmittals received | | | 12/12/2006 | | |
|
|
|
|
Alarm Plan Check | 12/6/2006 | | 12/6/2006 | | FAIL |
|
|
|
Fire Alarm Review #2
|
Miscellaneous action | | | 12/6/2006 | | |
|
|
|
Faxed copy of Failed 2nd review to Keith Olstrom of VanGuard.
|
Telephone call | | | 12/6/2006 | | DONE |
|
|
|
t/c w keith olstrom at vanguard protection - ###-#### - permit ready to be picked up - resubmittal
|
Plan resubmittals received | | | 11/28/2006 | | |
|
|
|
|
Alarm Plan Check | 11/21/2006 | | 11/21/2006 | | FAIL |
|
|
|
Start Fire Alarm Review
|
Telephone call | | | 11/21/2006 | | DONE |
|
|
|
t/c w Keith Olstrom at Vanguard Protection Group ###-#### - permit needed to be picked up and resubmitted
|
Miscellaneous action | | | 11/21/2006 | | |
|
|
|
Faxed copy of review to Vanguard Keith Olstrom
|
Case Summary | | | 11/13/2006 | | DONE |
|
|
|
|
Application received | | | 11/13/2006 | | |
|
|
|
|