INSP-Final Inspection | 3/12/2008 | 3/13/2008 | 3/13/2008 | A | PASS |
Forrest France
|
|
|
Incorrect device addresses at unit 102 amended while on site, relocated smoke alarms are acceptable, fire alarm work passed field testing, permit finaled.
|
INSP-Final Inspection | 3/10/2008 | 3/11/2008 | 3/11/2008 | A | NR |
Forrest France
|
|
|
Missing waterflow switch at one riser, smoke alarms at some locations do not comply with NFPA 72 2002 11.8.3.5 (5).
|
FIR-Aging Inspection | 5/15/2007 | 5/15/2007 | 5/16/2007 | | DONE |
Forrest France
|
|
|
Under construction.
|
Issue and Print Permit | | | 11/29/2006 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 11/14/2006 | | 11/27/2006 | | PASS |
|
|
|
11/27/2006 13:16:28 MWT - activity updated through activity FIRA22 from case FIR06-00889.
|
Alarm Plan Check | 11/27/2006 | | 11/27/2006 | | PASS |
|
|
|
Fire Alarm Review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/27/2006 | | |
|
|
|
Ready For Issue
|
Inspection Record Card- Fire | 11/27/2006 | | 11/27/2006 | | DONE |
|
|
|
|
Telephone call | | | 11/27/2006 | | DONE |
|
|
|
t/c w Charlie Bayne at SimplexGrinnell ###-#### - permit ready and no fee (new construction)
|
Permit Ready to Issue | | | 11/27/2006 | | DONE |
|
|
|
|
Application received | | | 11/14/2006 | | |
|
|
|
|