INSP-Final Inspection | 4/30/2007 | 5/1/2007 | 4/30/2007 | A | PASS |
Forrest France
|
|
|
UG fire supply line permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 3/30/2007 | 4/2/2007 | 4/2/2007 | A | FAIL |
Forrest France
|
|
|
OH hydrostatic test of the antifreeze system failed due to visible leakage at the system piping, OH hydro test of the wet system failed due to pressure drop at the guage below 200psi.
|
INSP-Supply line flush | 2/26/2007 | 2/27/2007 | 2/27/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed okay.
|
INSP-Sprinkler Rough-in | 12/1/2006 | 12/1/2006 | 12/1/2006 | P | PART |
Forrest France
|
|
|
UG fire supply line installation appears acceptable for cover, no approved plans on site for verification of size (4") or routing.
|
Sprinkler Plan Check | 11/16/2006 | | 11/16/2006 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/16/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/16/2006 | | 11/16/2006 | | DONE |
|
|
|
|
Telephone call | | | 11/16/2006 | | DONE |
|
|
|
t/c w Lilly at Shilo Automatic Sprinkler ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 11/16/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/16/2006 | | DONE |
|
|
|
|
Application received | | | 11/15/2006 | | |
|
|
|
|
Pending Assignment by SAM | 11/15/2006 | | | | |
|
|
|
|