Permit Information
Permit NumberFIR06-00917
StatusFinaled
Name M2 AUTOMATION
Site Address 802 W BANNOCK ST
Project NameHOFF BLDG-BASEMENT
Customer Number 
ePlanReview 
Description
This permit is to add audible visual notification appliances in a first floor office space tenant improvement located in the Historic Hoff Building. Building permit # BLD06-01628 is to remodel an existing 1279 sq ft portion of the basement for a future office tenant per approved plans. NO OCCUPANCY ALLOWED UNDER THIS PERMIT. A separate permit will be required for occupancy. Work to include, construction of interior noncombustible partitions to create individual office spaces, installation of suspended ceiling system and related lighting & dual-level switching, Miscellaneous related interior finishes. This building is fully fire sprinklered for high rise requirements any alterations or modifications to the sprinkler system WILL REQUIRE A Separate permit and shall be installed per approved plans as regulated by the fire department. RMH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/19/20086/24/20086/24/2008APASS
DetailsForrest France
Fire alarm testing completed satisfactory, permit finaled.
INSP-Final Inspection6/13/20086/17/20086/17/2008ANR
DetailsForrest France
Project is not ready for final inspection at this time per contractor, to be rescheduled.
Telephone call  6/2/2008 DONE
Telcon with Neal Timmerman. They received the duplicate set of approved City plans. They are now waiting for some additional information from Fire Sentry and expect to be ready for final inspection by the end of this week.
Plan assigned to (SAM)5/15/2008 5/15/2008 DONE
DetailsSam Rogers
Plan modification received 5-2-08, new fire contractor involved-now M2Automation, 1.5 hr admin fee charged per Sam Rogers///5-15-08 BAS
PLANS/APPL TAKEN TO FRONT DESK  5/15/2008 DONE
DetailsSam Rogers
Permit Ready to Issue  5/15/2008 DONE
Inspection Record Card- Fire5/15/2008 5/15/2008 DONE
DetailsBarbara Stitt
Telephone call  5/15/2008 DONE
Called Melissa (M2) and told her that permit is ready & fees due///5-15-08 @ 8:45am BAS
CHANGE STATUS TO (ISS)  5/15/2008  
already issued
Plan resubmittals received  5/2/2008  
Plan Modification: Received application and letter; taken to fire review
(F) Reprint permit  5/2/2008 DONE
Alarm Plan Check5/2/2008 5/2/2008 PASS
DetailsSam Rogers
Resubmitted letter from Fire Sentry suthorizing this project to be turned over to M2 as the new Vendor and Installer, to complete the installation and inspection process. (Doc. Attached). No fee involved, permit left in Issued status, awaiting call for inspection.
INSP-Alarm Testing2/12/20072/13/20072/13/2007PFAIL
DetailsTroy Cobbley
See Mike Timmerman's inspection report dated today for corrections required.
Inspection2/13/20072/13/20072/13/2007 FAIL
Fire Alarm Inspection Basement Office Space Correction Item 1.) Office visual devices not in syncronization with corridor, can be seen through glass window and glass door. Fail Item 2.) Alert tone incorrect. Needs to be temporal Whoop. Fail
INSP-Final Inspection2/8/20072/9/20072/9/2007ACANC
DetailsTroy Cobbley
To be rescheduled. Contractor could not do a late afternoon inspection.
Issue and Print Permit  12/5/2006 DONE
Plan assigned to (Mike)11/17/2006 12/1/2006 PASS
12/1/2006 12:18:18 MWT - activity updated through activity FIRA22 from case FIR06-00917.
Alarm Plan Check12/1/2006 12/1/2006 PASS
Fire Alarm Review
PLANS/APPL TAKEN TO FRONT DESK  12/1/2006  
Ready for Issue
Inspection Record Card- Fire12/1/2006 12/1/2006 DONE
Telephone call  12/1/2006 DONE
t/c w John Lopez at Fire Sentry Systems ###-#### - permit ready and fees given ($150.00)
Permit Ready to Issue  12/1/2006 DONE
Application received  11/17/2006